RECEIVING THE UNIT

When you receive the unit, unpack it checking that the packaging is intact. Inspect it and make sure nothing is missing.

In addition to the unit, y

ou will also find:

-  

One bag containing the anchor bracke

ts or fixing b

rackets supplied unassembled, for installation in situ

 

on the machine’s chassis. This includes 8 M5 cross-head bolts t

o fix 

the unit to the desired surface.

-  

Another bag with the differential pressure switch, the transparent pressure tube and the 2 thread/sheet bolts f

or fixing it.

-  

An individual absolut

e filter te

st cer

tificate.

RECEIVING THE UNIT

The unit is a Plug&Play device, meaning that you do not need t

o configu

re anything.

We recommend that you open the access panel to check that nothing has moved during transport, making sure

 

that the pr

efilte

r, the GRSystem and t

he absolute filter a

re corr

ectly positioned and fi

xed in place.

The access panel is opened by removing the 8 M6 Allen bolts (4 on each side), with it being important

 

to retighten them correctly to ensure the seal of the unit.

The unit starts up automatically when powered up.*

Before starting it up, all of the unit's access panels must be closed.

Keep the start-up switch in the stop position and connect the unit.

Connect the main external power switch to the unit, keeping its start-up switch in the stop position. Once this has 

been done, check that  the voltage on the unit’s electrical input terminals matches the voltage indicated on the 

 

nameplate (the minimum permitted voltage will be 10% less than the nominal voltage indicated on the nameplate).

Check that the earth connection is connected correctly.

Once all these checks have been done, remove the unit’s stop position (switch it ON).

The fan will not start if the duct network is not completely closed, as the connection of the fan without load can cause 

overcurrents that could damage the motor.

(*) See in the user manual the different types of connection. The setting of the pressure switches is: 

 

EMERGENCY OPERATIONS

If you notice any problem on the unit, switch it off using the emergency stop device.

These emergency operations will generally be due to a problem with the electrical circuit, in which case there will be 

problems with  the motors. You will therefore need to disconnect the power in order to locate the fault, which may be 

inside the unit (short circuits, etc.) or external to the unit (power supply issues, voltage variations, etc.).

In the ev

ent of a fi

re, it must be extinguished using suitable extinguishers. 

CONTACT DETAILS:  +34 93 551 03 40  - www.zonair3d.com  - [email protected]

AIR PRO 100-300

_S

TA

R

T-UP GUIDE_220307

                             

 Without ducts 

    50 Pa                 100 Pa

AIR PRO 100                201                        181                    160
AIR PRO 300                240                           222                    194

Summary of Contents for AIR PRO 100

Page 1: ...P A P A P100 P100 P300 P300 P100 300 100 P100 P300 P100 P AIR PRO PUESTA EN MARCHA START UP PROCEDURE MESSA IN FUNZIONE PROCEDIMENTO DE ARRANQUE ZONAIR3D ...

Page 2: ......

Page 3: ...idas a regleta 3 Cable de red a 230v 2 fases tierra 4 Interruptor general ON OFF 5 Tapa de registro de la PCB 4 tornillos M5 6 Toma de presión positiva del H14 7 Presostato diferencial Switch 8 Conexión al presostato de presión positiva H14 9 Roscas M5 de fijación de las escuadras de anclaje 10 Toma de presión negativa del H14 11 Conexión al presostato de presión negativa H14 12 Led rojo indicativo...

Page 4: ... unidad manteniendo en posición de paro el interruptor de puesta en marcha de esta Realizado esto comprobar que la tensión en los bornes eléctricos de entrada del equipo corresponden con la establecida en la placa de características la tensión mínima admitida será de un 10 inferior a la nominal indicada en la placa de características Se comprobará que la toma de tierra está bien conectada Una vez ...

Page 5: ... cable 2 phases earth 4 Main ON OFF switch 5 PCB registration cover 4 M5 bolts 6 H14 positive pressure tap 7 Differential pressure switch 8 Connection to the H14 positive pressure switch 9 M5 threads for fixing the anchor brackets 10 H14 negative pressure tap 11 Connection to the H14 negative pressure switch 12 Red LED to indicate HEPA14 filter change Maintenance Maintenance PRODUCT RANGE FLOW m 3 h...

Page 6: ... external power switch to the unit keeping its start up switch in the stop position Once this has been done check that the voltage on the unit s electrical input terminals matches the voltage indicated on the nameplate the minimum permitted voltage will be 10 less than the nominal voltage indicated on the nameplate Check that the earth connection is connected correctly Once all these checks have b...

Page 7: ...asi terra 4 Interruttore generale ON OFF 5 Copertura accesso PCB 4 viti M5 6 Presa di pressione positiva dell H14 7 Switch pressostato differenziale 8 Collegamento al pressostato di pressione positiva H14 9 Filettature M5 per il fissaggio delle staffe di ancoraggio 10 Presa di pressione negativa dell H14 11 Collegamento al pressostato di pressione negativa H14 12 Led rosso per indicazione cambio de...

Page 8: ...ttore di avviamento dell unità in posizione di arresto Quindi verificare che la tensione ai morsetti elettrici di ingresso del dispositivo corrisponda a quella indicata sulla targhetta dati la tensione minima ammissibile sarà del 10 inferiore alla tensione nominale indicata sulla targhetta dati Controllare che la messa a terra sia collegata correttamente Una volta effettuati tutti i controlli rimuo...

Page 9: ...ma régua de terminais 3 Cabo de alimentação de 230v 2 fases terra 4 Interruptor geral ON OFF 5 Tampa de registo do PCB 4 parafusos M5 6 Tomada de pressão positiva H14 7 Pressostato diferencial Switch 8 Ligação ao pressostato de pressão positiva H14 9 Roscas M5 para fixação dos suportes de ancoragem 10 Tomada de pressão negativa do H14 11 Ligação ao pressostato de pressão positiva H14 12 LED vermelh...

Page 10: ...uptor geral de alimentação externa à unidade mantendo o interruptor de colocação em funcionamento da unidade na posição de paragem Após efetuar este passo verifique se a tensão nos terminais elétricos de entrada do equipamento corresponde à indicada na placa de características a tensão mínima admissível será 10 inferiorà tensão nominal indicada na placa de características Verifique se a ligação à te...

Page 11: ......

Page 12: ...AIR PRO 100 300 ZONAIR3D ...

Reviews: