Step #7
Once unit is ready for testing:
• Verify that the pit is free of ANY debris
and power cords are properly placed out
of way.
• With control panel ON, verify that pump(s)
operate manually using the HAND mode
inside the control panel.
• With control panel ON, verify that the
pump(s) operate automatically using the
AUTO mode inside the control panel.
• Third float will activate the ALARM
BEACON on control panel on a 3-float system.
• Fill basin with water and confirm that pumps are operating (and alternating if a duplex system) properly.
Do not run dry for more than a few seconds as this will damage the pump’s mechanical seal.
"OFF" (FLOAT HEIGHT 15")
"ON" (FLOAT HEIGHT 24")
"LAG/ALARM" (FLOAT HEIGHT 27")
"ALARM" (FLOAT HEIGHT 33")
FACTORY INSTALLED PVC
FLOAT TREE ASM
NOTE: HEIGHT IS FROM BOTTOM
OF THE BASIN
ON SIMPLEX, 3-FLOAT SYSTEMS,
THERE IS NO "LAG", ONLY ALARM.
ON DUPLEX, 3-FLOAT SYSTEMS,
THESE FUNCTIONS ARE COMBINED.
(SEE WIRING DIAGRAM)
sk2280
BACKFILL MATERIAL
CONCRETE GROUT AS
REQUIRED PER ENGINEER'S
SPECIFICATION
COMPACTED SUB-BASE
MINIMUM 12" OR 6"
WHEN USED WITH CONCRETE
HOLD-DOWN PAD
SLOPE AND SIZE OF EXCAVATION
AS PER OSHA AND ENGINEER'S
SPECIFICATION. IN THE ABSENCE
OF THESE. CONSIDER CONDITION
OF SOIL. DEPTH OF EXCAVATION
AND SAFETY CONSIDERATIONS.
BASIN ANTI-FLOATATION DEVICE
COMPACTED SUB-BASE
AND/OR
CONCRETE SLAB AS PER
ENGINEER'S SPECIFICATION
ADJACENT STRUCTURE, FOUNDATION
FOOTING OR PROERTY LINE
12" MINIMUM BACKFILL
COMPACTED TO A MINIMUM
SOIL MODULUS OF 700 PSI
FINISHED GRADE
5'-0"
MINIMUM
45°
MINIMUM
FIBERGLASS BASIN AS
REQUIRED PER
ENGINEER'S SPECIFICATION
Three - Way Ball Valve Flow
(Used with Duplex Systems)
Red
X
indicates closed.
All open
Left closed
Right closed
Discharge closed
X