WD & WH MODEL INSTALLATION

WIRING DIAGRAM FOR MODELS

WD - 230V, 1 Ph, 60 Hz.

WH - 200/208V, 1 Ph, 60 Hz.

Models WD & WH are fully automatic. A fl oat switch is in clud ed and 

fac to ry wired in the pump circuit to provide automatic operation 

once the fl oat switch is secured prop er ly to the outlet pipe. Use the 

di a gram above to secure the fl oat switch properly and obtain the 

proper tether to cus tom ize the on-off cycle to each ap pli ca tion.

Determining Pumping Range

in Inches (1 inch - 2.5 cm)

Tether Length 

5  10  15 20 22

Pumping Range  9 13.5 18 22 24

max.

Use only as a guide. Due to weight of 

ca ble,  pump ing  range  above  hor i zon tal 

is not equal to pumping range be low 

hor i zon tal. Ranges are based on test ing in 

nonturbulent con di tions. Range may vary 

due to water tem per a ture and cord shape. 

As teth er length in creas es, so does the 

vari ance of the pump ing range.

min.

START

RUN

BLUE

MOTOR

(WHITE)

RED

(BROWN)

O.L.

YELLOW

(BLACK)

SWITCH

FLOAT 

BLACK

BLACK

WHITE

CAPACITOR

BLUE
(1)

(2)

RED

RUN

WHITE

GREEN

L1

L2

(3)

011835

Note: Failure to keep within proper teth er limits 
may prevent reliable switch op er a tion.

Note: Cable must be mounted in hor i zon tal 
position.

22" MAX.

5" MIN.

20 AMP SWITCH (WD & WH MODELS)

SK305

THREE PHASE WIRING INSTRUCTIONS

  FOR YOUR PROTECTION, ALWAYS 

DIS CON NECT PUMP FROM ITS POWER SOURCE 

BE FORE  HAN DLING.

To automatically operate a nonautomatic three phase pump, a 

control panel is required.  Follow the in struc tions pro vid ed with the 

panel to wire the system.  For automatic three phase pumps see 

automatic 3 phase wiring di a gram located to the far right.

Before installing a pump, check the pump rotation to en sure that 

wiring has been connected prop er ly to power source, and that 

the green lead of pow er cord (See wiring di a gram), is con nect ed 

to a valid ground. Mo men tari ly en er gize the pump, observing the 

di rec tions of kick back due to start ing torque. Ro ta tion is correct if 

kick back is in the op po site direction of rotation arrow on the pump 

cas ing. If rotation is not correct, switching of any two power leads 

other than ground, should provide the proper rotation.

All three phase pumps require motor starting devices with motor 

overload pro tec tion. See FM0486 for duplex in stal la tions.  Pumps 

must be in stalled in ac cor dance with the National Electrical Code 

and all ap pli cable local codes and or di nanc es. Pumps are not to 

be installed in locations clas si fi ed as haz ard ous in accordance 

with National Elec tri cal Code, ANSI/NFPA 70.

NONAUTOMATIC

3 PHASE

AUTOMATIC

3 PHASE

MOTOR

(3)

BLUE

RED

BLACK

GREEN

L1

L2

(1)

(2)

YELLOW

L3

WHITE

RED

013071

SINGLE PHASE WIRING INSTRUCTIONS

  FOR YOUR PROTECTION, ALWAYS DIS CON NECT PUMP FROM ITS POWER SOURCE BE FORE HAN DLING.  Single phase 

pumps are sup plied with a 3-prong ground ed plug to help protect you against the possibility of electrical shock. DO NOT UNDER ANY CIRCUM STANCES 

RE MOVE THE GROUND PIN.  The 3-prong plug must  be inserted into a mating 3-prong grounded re cep ta cle. If the in stal la tion does not have such 

a receptacle, it must be changed to the prop er type, wired and ground ed in accordance with the National Elec tri cal Code and all applicable local codes 

and ordinances.

  “Risk of electrical shock”  Do not remove power supply cord and strain relief or connect conduit directly to the pump.

  Installation and checking of electrical circuits and hardware should be performed by a qualifi ed licensed elec tri cian.

  Units supplied without a plug (single and three phase) and single phase nonautomatic units with a 20 amp plug must have a motor 

control and liquid level control provided at time of installation. The control device should have suitable voltage, ampere, frequency, grounding and 

horsepower rating for the pump to which it is connected.

IMPORTANT NOTICE: Some insurance policies, both commercial and residential, extend coverage for damages incurred by product failure. You will need to 

have possession of the product to support your claim in most cases. Zoeller Pump Co. will exchange the unit or refund the original purchase price once the claim 

is settled with the insurer in the case where you need to retain possession of the product to support a damage claim you submit to your insurance company.

006848

Summary of Contents for 6355

Page 1: ...unded in accordance with the National Electrical Code and all applicable local codes and ordinances Three phase pumps require motor starting devices with motor overload protection See FM0486 for duplex installations 6 The tank is to be vented in accordance with local plumbing code Pumps must be installed in ac cordance with the National Electrical Code and all applicable local codes and ordinances...

Page 2: ...tempt to service or otherwise disassemble pump Service must be performed by Zoeller Authorized Service Stations Go to www zoeller com zcopump TechSupport authsslisting htm to find the Authorized Service Station in your area SERVICE CHECKLIST EASY DO S DON T S FOR INSTALLING A SUMP PUMP 1 DO read thoroughly all installation material provided with the pump 2 DO inspect pump for any visible damage ca...

Page 3: ...LE MUST ALSO BE BELOW THE BASIN COVER AND CLEANED PERIODICALLY High Head unit see 3 under Caution on front page Water stream will be visible from this hole during pump run periods 5 Securely tape or clamp power cord to discharge pipe clear of the float mechanism s 6 Use full size discharge pipe 7 Basin must be in accordance with applicable codes and specifications 8 Pump must be level and float me...

Page 4: ...correct switching of any two power leads other than ground should provide the proper rotation All three phase pumps require motor starting devices with motor overloadprotection SeeFM0486forduplexinstallations Pumps mustbeinstalledinaccordancewiththeNationalElectricalCode and all applicable local codes and ordinances Pumps are not to be installed in locations classified as hazardous in accordance w...

Reviews: