© Copyright 2019 Zoeller
®
Co. All rights reserved.
1.1) Select a location for the pump that is below the evaporator drain and/or furnace drain.
1.2) The unit has two mounting brackets built into the deck so the pump can be attached to the wall or side of the appliance.
Refer to Figure 1.2.
2.1) To prevent pipe blockage, modify the end of the pipe or tubing as shown in Figure 2.1.
2.2) Plumb, flexible tube or pipe, from the condensate drain and/or from the furnace drain to the inlet hole(s) on the pump.
Refer to Figure 2.2.
Figure 1.2
Figure 2.2
Figure 2.1
Note:
The drain line(s) should have a continuous downward slope to allow for gravity flow.
Note:
Local codes may require the use of a condensate neutralizer when using this pump.
Note:
Make sure the drain lines from the A.C. condenser are supported above the reservoir and no weight from the drain line is
directed to the bottom of the reservoir.
SK3177
SK1765
SK3178
STEP 1
Mounting Location
STEP 2
Installation of Condensate Drain Lines
CONDENSING GAS
FURNACE
OVERFLOW
MAIN CONDENSATE DISCHARGE
CONDENSATE TRAP
GFCI
OUTLET
MOUNTING BRACKETS
Note
: Insert, Tubing or Pipe,
Through the Inlet until the Tip
Contacts Bottom of Reservoir.
Drain Pipe
45°
CONDENSING GAS
FURNACE
A/C CONDENSER
MAIN DRAIN FROM COIL
OVERFLOW DRAIN FROM
COIL WHEN REQUIRED.
GFCI
OUTLET
MAIN DRAIN FROM FURNACE
CONDENSATE NEUTRALIZER
CARTRIDGE (IF REQUIRED)
OVERFLOW DRAIN
FROM FURNACE