3
© Copyright 2018 Zoeller
®
Co. All rights reserved.
1. Read all instructions before beginning installation.
2. Be sure the installation does not exceed a maximum
of 15 feet of vertical lift.
3. Be sure the pump is level within 1/8" for the length of
the condensate pump.
4. Use soapy water when cleaning unit. Refer to
maintenance guidelines.
5. For best results, drain and discharge lines should have
a continuous downward slope.
1. DO read all installation material included with the pump.
2. DO inspect unit for any visible damage caused by
shipping. Contact dealer if unit appears to be damaged.
3. DO clean all debris from the pump reservoir.
4. DO always disconnect pump from power source before
handling. DO always connect to a separately protected
and properly grounded ground fault protected circuit.
DO NOT ever cut, splice or damage power cord. DO
NOT carry or lift pump by its power cord. DO NOT use
an extension cord with this condensate pump.
Ten Helpful Hints or Easy Installation
Do’s and Do Nots or Installing Unit
5. DO NOT use
a discharge pipe smaller than the pump
discharge size.
6. DO test pump immediately after installation to be sure
that the system is working properly.
7. DO review all applicable local and national codes and
verify that the installation conforms to each of them.
8. Do not use Flexible tubing larger than 3/8".
6. Test operation of pump per STEP 5.
7. Do not overtighten check valve after cleaning. Refer
to maintenance guidelines.
8. Plug pump into a constant voltage source. Do not
plug into a device that runs intermittently.
9. The model number and date code can be found on
the pump I.D. label.
10. For best results, the highest point of the discharge
line should be higher than 5’ above floor.