ZMIO310 Vertical Bus Expansion Module User Manual V1.0
Impedance of voltage (input)
>1M
Ω
Range of voltage (input)
Dual-pole: -5V~5V, -10V~10V. Single-pole: 0~5V, 0~10V.
Range of current (input)
0~20mA, 4~20mA
Resolution
16-bit
Sample time
1ms/channel
Precision (common temperature 25° C)
Voltage ± 0.1%, current ± 0.1% (full range)
Precision (environmental temperature
0~55° C)
Voltage ± 0.3%, current ± 0.8%
Internal Power
0.4W
Power
0.7W
Isolation
Coupler isolation
Service
Firmware upgrade
4.3.3.
Installation Size
→
Installation Step:
➢
Please use 35mm standard DIN guide rail.
➢
Open guide rail buckle of AD module, then embed AD module in the DIN guide rail.
➢
Press fit guide rail buckle of AD module, then fix AD module in the DIN guide rail.