22
InBio Pro Series Access Control Panels INSTALLATION guIDE
RS485 Connection
1
2
4
8
16
32
Restore Factory Setting
RS485 Terminal Resistance
Restore factory setting
1.
If you forget the IP address of the InBio Pro panel or the device does not work
normally, you can use the number 7 DIP switch to restore InBio Pro Panel to
factory default settings. The parameters which gets reset are device IP address,
communication password, gateway, and subnet mask.
2.
The switch is OFF by default. When it is moved up and down for three times
within 10 seconds and fi nally returned to OFF position, the factory settings will
be restored after the access control panel is restarted.
To reset factory settings
Turn #7 switch ON and OFF
Repeat process 3 times
Figure 32
Figure 33