Ziton ZP7BMR-50 Quick Start Manual Download Page 3

 

1. System Description. 

 
The ZP7BMR-50/100 Detector comprises a Transmitter and Receiver contained within one enclosure. 
 
The Detector installs to the building fabric between 0.5 and 0.6 metres from the ceiling. 
 
The Transmitter emits an invisible infrared light beam that is reflected via a prism(s) mounted directly opposite 
and with a clear line of sight. The reflected infrared light is detected by the Receiver and analysed. 
 
The Detector has maximum lateral detection of 7.5 metres either side of the beam. 
 

2. System Operation. 

 
Smoke in the beam path will reduce the received infrared light proportionally to the density of the smoke. The 
Detector analyses this attenuation or obscuration of light and acts accordingly. 
  
Alarm thresholds of 25%, 35%, and 50% can be selected to suit the environment, where 25% is the most 
sensitive. If the received infrared signal reduces to below the selected threshold, and is present for 
approximately 10 seconds, a Fire condition is activated. 
 
If the infrared beam is obscured rapidly to a level of 90% or greater for approximately 10 seconds a Fault 
condition is activated. 
This condition can be entered in a number of ways, for example, an object being placed in the beam path, 
transmitter failure, loss of the prism(s), or sudden misalignment of the Detector. The fault condition will reset 
within 10 seconds of the condition being rectified. 
 
The Detector monitors long term degradation of signal strength caused by component ageing or build up of dirt 
on optical surfaces. This operates by comparing the received infrared signal against a standard every 15 
minutes. When the detector is showing AGC fault, the detector will still operate correctly indicating Alarm and 
Fault as normal. 
 

3. Detector Positioning. 

 
It is important that the ZP7BMR-50/100 Detector is positioned correctly to minimise the detection time. 
 
Experiments have shown that smoke from a fire does not rise directly upwards, but fans out or mushrooms due 
to air currents and heat layering effects. The time to signal a fire condition depends on the location of the 
Detector within the premises, the volume of smoke produced, construction of the roof, and ventilation 
arrangements. 
 
The maximum distance either side of the beam axis is found to be typically 7.5 metres for satisfactory detection 
under flat ceilings. 
 
 
 
 
 
 
 
 
 
Smoke layering, where smoke does not reach the ceiling level due to layers of static hot air is overcome by 
mounting the Detector at the recommended height below the ceiling of between 0.5 and 0.6 metres, bringing 
the infrared beam below the heat layer and into the smoke layer. 
 
However, in all installations the latest national fire standards 

must

 be consulted. If there is any doubt on the 

correct mounting height, positioning may be determined by smoke tests. 

Single Beam 

15 m 

15 m 

0.5 

 7.5 m

Multiple Beams 

0.3 

 0.6 m

0.5 

 7.5 m

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ZP7BMR-50

Page 1: ...Range 50 100 Metres Unique simple alignment Loop powered Selectable alarm thresholds Low current consumption Automatic contamination compensation ZITON ZP7BMR 50 100 Loop Powered Analogue Addressable...

Page 2: ...ism Targeting page 5 6 Alignment page 5 to 7 7 System Testing page 7 8 Connection and configuration Settings page 8 9 Detector Back View page 9 10 Address settings page 10 11 Clearances page 11 12 Tec...

Page 3: ...ondition being rectified The Detector monitors long term degradation of signal strength caused by component ageing or build up of dirt on optical surfaces This operates by comparing the received infra...

Page 4: ...creased from 7 5 metres either side of the beam to 7 5 7 5 x 20 100 metres 9 metres Therefore with a roof pitch of 20 degrees the lateral coverage can be increased from 7 5 metres either side of the b...

Page 5: ...ON OFF ON OFF ON X Logic 1 0 1 0 1 0 1 X The Detector Head Assembly is now ready for installation If configuration switches 3 and 4 require resetting after installation a power down reset is required...

Page 6: ...horizontal and vertical thumbwheels until the Amber LED is flashing Both the Red and Amber LED will be OFF when no signal is being received The Red LED will start to flash when a weak signal is receiv...

Page 7: ...be receiving a fringe reflection from another object FLICKERING RED AMBER This state can occur sometimes It means that the infrared power is stepping through the optimum setting for the current orient...

Page 8: ...n filter to correspond with the Detector alarm threshold see fig 3 Place the filter over the receiver optics Top of Detector Head opposite end to the status indication LED s at the correct obscuration...

Page 9: ...itch with the following features The address settings is set up via the 8 way DIP switch on the lower part of the beam See Fig 4 8 3 Typical Loop Wiring Fire Panel Connections Loop Output Input to Nex...

Page 10: ...9 Detector Interface Assembly Configuration Settings DIP SWITCH SETTINGS X X X X X X X X X X X X X X X X X X X 2 X 1 3 4 Fig 4 www acornfiresecurity com www acornfiresecurity com...

Page 11: ...0001011X 19 1100100X 62 0111110X 105 1001011X 20 0010100X 63 1111110X 106 0101011X 21 1010100X 64 0000001X 107 1101011X 22 0110100X 65 1000001X 108 0011011X 23 1110100X 66 0100001X 109 1011011X 24 000...

Page 12: ...ameter clearance down the entire beam path If there are highly reflective objects within 1 metre diameter of the beam path for the first 20 metres of the beam path for the ZP7BMR 100R then tests shoul...

Page 13: ...rt 5 use 25 and 35 default thresholds The threshold of 50 is recommended for hostile and extreme environments When in normal run mode the fire panel controls the Red LED flashing Amber LED flashing on...

Reviews: