background image

Installation Sheet  

No.: 1780 iss 02 

ZP755HAV-2 Addressable Omni-directional Sounder Beacon 

Installation sheet 

 

501-1780ZE-1-02 

ZP755HAV-2 Page 

4  12/12/2005 

Number of Sounders Per Loop 

See figure 5. 

The ZP755HAV-2 sounder can be powered directly 
from the loop of a ZP5 or ZP3 panel.  The table below, 
read in conjunction with figure 5, gives the quantity of 
detectors and sounders that can be connected to a 2 
core screened loop of: 

1000 metres cable size 1.5mm

2

 

1. 

10 metres panel to devices 

 

80 detectors and 20 sounders 

 

100 detectors and 15 sounders 

2. 

100 metres panel to devices 

 

80 detectors and 20 sounders 

 

100 detectors and 15 sounders 

3. 

200 metres panel to devices 

 

60 detectors and 20 sounders 

 

100 detectors and 15 sounders 

4. 

300 metres panel to devices 

 

40 detectors and 20 sounders 

 

110 detectors and 15 sounders 

Figure 5 

 