background image

Installation Sheet  

No.: 1780 iss 02 

ZP755HAV-2 Addressable Omni-directional Sounder Beacon 

Installation sheet 

 

501-1780ZE-1-02 

ZP755HAV-2 Page 

1  12/12/2005 

 

Product description 

Description 

Across the world disability legislation increasingly 
requires visual alarm signals to be employed to 
ensure equal response from people with hearing 
impairment. Conforming to EN54 Part 3, the 
ZP755HAV-2 Addressable Sounder Beacon is 
perfectly suited for this application and indeed any 
involving high levels of background noise. 

Application 

It provides both audible and visual warnings from a 
single, addressable, loop wired unit. 

Featuring an identical profile to the ZP755 HA horn 
sounder, the ZP755HAV can minimise the number of 
installation points required throughout a building, 
significantly lowering both the capital value of 
equipment and the loop wiring costs of the completed 
system.  

The units high efficiency acoustic design and sound 
gun transducer as well as the low current Light 
Emitting Diode (LED) visual element, enables 
combinations of up to 20 sounder beacons to be 
connected to a one kilometer loop of 1.5mm

2

 cable.  A 

plug-in base accepts all loop and screen connections, 
prior to the horn sounder beacon connection. 

The ZP755HAV-2 range features a unique self-test  
facility - automatically activated during routine sounder 
testing. A built in microphone circuit measures sound 
output level and automatically signals the sounder 
address and location to the control panel, should 
volume fall below the expected test level.  

In systems where loop lengths or current 
requirements are excessive, ZP755HAV-2 sounders 
can be powered directly from an external power 
supply. All ZP755HAV-2 sounders incorporate switch 

settings enabling them to be assigned a unique 
address, which is polled by the panel every two 
seconds. 

Continuous, intermittent and two-tone outputs are 
available, from which any combination can be chosen 
to provide alert and evacuate, two stage alarms. All 
sound types comply with BS 5839 Part 1:1988 
recommended frequencies (in accordance with EN54 
Part 3). 

The ZP755HAV-2 features the wide sound distribution 
design, with an 'all around' sound output of 90 dBA. 

Moulded in high impact thermoplastic, the sounder is 
available in either red or white. 

Specifications 

Design specification: 

EN54 Part 3 

Designation:  

 

Addressable Omni-directional 
Sounder Beacon 

Model No/Part No.: 
ZP755HAV-2R (Red)  

178001 

ZP755HAV-2W (White)  178101 
Compatibility: 

All ZP3 analogue 
addressable systems  

Mounting: 

Surface - with plug-in base 

SPB-2R (red)  

180801 

SPB-2W (white)  

180901 

Addressing method: 

7 way Dip switch 

Wiring: 

2 core loop 

Monitoring: 

ZP loop - open and short circuit 
fault sound output level - self test 
facility 

Sound output: 

 

Tone 1 

continuous 980 Hz 

Tone 2 

intermittent 980 Hz (0.5 secs 
on/off) 

Tone 3 

two tone warble 980 Hz/670 Hz 

Sound distribution:   
ZP755HAV  

wide 

CNPP anechoic sound levels: 

Reviews: