background image

4 / 4 

 

P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14 

Figure 7: Detector/sounders per loop 

 

A. 

Cable length panel to first sounder 

B. 

Cable length first to last sounder 

C. 

Cable length last sounder to panel 

1. 

Detectors and Sounders 

Table 4: Maximum detectors and sounders per loop 

Quantity allowed [1] 

10 m 

980 m 

10 m 

80 detectors and 20 sounders 

100 detectors and 15 sounders 

100 m  

800 m 

100 m 

80 detectors and 20 sounders 

100 detectors and 15 sounders 

200 m 

600 m 

200 m 

60 detectors and 20 sounders 

100 detectors and 15 sounders 

300 m  

400 m  

300 m 

40 detectors and 20 sounders 

110 detectors and 15 sounders 

[1] Using a two-core shielded loop of 1000 meters cable size 
1.5  mm² 

Specifications 

 

Operating voltage 
 

External supply 

 

Loop supply, ZP protocol 

 
18 to 30 VDC 
19.5 to 20.5 V pulsed, max. 4 V line 
loss 

Current (line powered) 

Quiescent (RMS) 
Alarm (RMS) 
Alarm (excluding device 
address) 
Alarm (at device address) 

 
820 

μA 

9.6 mA 
19.6 mA max. 
 
26 mA max. 

Current (externally powered) 
 

Quiescent (RMS) 

 

Alarm (RMS) 

 

Maximum number 

 
470 μA 

500 μA 
20 per 1 km loop (subject to cable 
size and sounder spacing) 

Sound output  
 

Tone 1 

 

Tone 2 

 

Tone 3 

90 dBA (all around) 
Continuous 980 Hz. 
Intermittent 980 Hz. (0.5 sec on/off) 
Two-tone warble 980 Hz./670 Hz. 

Sound distribution 

Wide 

Light output 

Equivalent to 1J xenon element 

Strobe frequency 

Flash rate 1.3 seconds 

CNPP anechoic sound levels 

See Figure 8  

Monitoring 
 

ZP loop 

 

Sound output level 

 
Open and short circuit fault 
Self test facility 

Compatibility 

Ziton analogue addressable 
systems 

Addressing method 

7-segment DIP switch 

Mounting 

Surface with plug-in base 

Wiring 

Two-core shielded loop 

Construction 
 

Material 

 

Colour 

 

Weight 

 

Dimensions (Ø × D) 

 
Moulded thermoplastic 
Red or polar white 
305 g 
127 × 113 mm 

Operating environment
 

Temperature 

 

Relative humidity 

 
−10 to +60°C 
10 to 95%, noncondensing 

Storage temperature 

−20 to +70°C 

Figure 8: CNPP anechoic sound levels 

 

Regulatory information 

This section includes both regulatory information and a 
summary on the declared performance according to the 
Construction Products Regulation 305/2011. For detailed 
information refer to the product Declaration of Performance. 

 

Certification 

 

Certification body 

0370 

Declaration of 
Performance number 

360-5201-0499 

Year of first CE marking  14 

Product Identification 

ZP755HAV-2

 

Intended use 

See DoP point 3 

Essential characteristics  See DoP point 9 

Manufacturer 

Gulf Security Technology Co.,Ltd 
80, Changjiang East Road, 
QETDZ, Qinhuangdao, 
Hebei Province, China 066004 

Authorized EU manufacturing representative:  
UTC Fire & Security B.V.  
Kelvinstraat 7, 6003 DH Weert, Netherlands 

European Union 
directives 

1999/5/EC (R&TTE directive): Hereby, UTC 
Fire & Security declares that this device is in 
compliance with the essential requirements 
and other relevant provisions of Directive 
1999/5/EC. 

 

2002/96/EC (WEEE directive): Products 
marked with this symbol cannot be disposed 
of as unsorted municipal waste in the 
European Union. For proper recycling, return 
this product to your local supplier upon the 
purchase of equivalent new equipment, or 
dispose of it at designated collection points. 
For more information see: 
www.recyclethis.info. 

 

Contact information 

For contact information, see www.utcfssecurityproducts.eu. 

1

6

5

O

105

O

75

O

45

O

1

5

O

13

5

O

dBA

70

75

80

85

70

75

80

85

90

90

Reviews: