ZP755BV-4 Addressable Base Sounder with 
Visual Indicator Installation Sheet 

 

Description 

The ZP755BV-4 is an addressable base sounder with visual 
indicator, designed for use in Ziton analogue addressable fire 
detection and alarm systems.  

Note: 

The visual indicator of this product does not comply with 

EN 54-23 and must not be used in fire alarm installations 
where fire notification beacons are required. 

The sounder includes a volume control, an address-setting 
switch, programmable tone settings, and a pair of jumpers to 
select the operating power — from the analogue addressable 
loop or an external supply. The device plugs into a base that is 
purchased separately. See Table 1 for a list of model numbers. 

Table 1: Models 

Number 

Description 

Sounder, 
 

ZP755BV-4P 

 
Base sounder/Visual indicator, Polar white 

Cover,  
 

ZP755-COV-P 

 
 

ZP755-COV-R 

 
Cover for ZP755B Base sounder  
with no detector, Polar white 
Cover for ZP755B Base sounder  
with no detector, Red 

Base, 
 

SPB–2P 

 
Base, Polar white 

 

Installation 

To install the device: 

1.  Wire the base 

2.  Set the operating power 

3.  Set the address 

4.  Set the operating mode 

5.  Set the tone 

6.  Set the volume 

7.  Mount the sounder onto the base 

The details of each step are given below 

Wiring the base 

Connect the loop wiring for the base as shown in Figure 1. 
There is no wiring between the sounder and base. 

Figure 1: Loop wiring for the base 

 

1. 

Ext. 24 VDC+ IN/OUT 

4. 

Ext. 24 VDC ground IN/OUT 

5. 

Loop+ IN/OUT 

7. 

Shield 

8. 

Loop − IN/OUT 

Setting the operating power 

The sounder includes a pair of power selection jumpers, J1 
and J2. To select the source of the sounder operating power, 
position the jumpers as shown in Figure 2. 