Chapter 3: Configuration and commissioning
58
ZP2-A Series Installation Manual
The Disable/Enable menu
Use the Disable/Enable menu to disable and enable the system features and
devices. Disabled features and devices do not indicate faults or fire alarms.
Note:
Changes to disable/enable configuration at this user level are not stored in
the control panel configuration and are not included in any saved configuration
files.
The following features or devices can be disabled or enabled from this menu:
• Zones
• Devices (individually or by device type)
• Control panel inputs
• Default output groups (sounder, fire routing, or fire protection)
Notes:
Outputs can only be enabled or disabled at Installer level.
Only the default output groups can be enabled or disabled at Maintenance level
(program output groups cannot be enabled or disabled). All output groups
(default and program) can be enabled or disabled at Installer level.
If disabling zones in alarm, you must manually reset the control panel to
complete the operation.
Remote disablement is available at Installer level. See “Remote disable/enable
Disabling a system feature or device
To disable a feature or device:
1. Select Disable/Enable from the Main menu.
2. Select Disable.
3. To disable a device by type select Zones, and then press F4 (Devices) to
disable the device type for selected zones or F3 (All zones) to disable the
device type for all zones.
Use soft keys F2-F4 to select the device types to be disabled: MCP (manual
call points), Smoke (ionization detectors, optical detectors, multisensors), or
Auto detect (ionization detectors, optical detectors, heat detectors,
multisensors).
4. For other disablements (zones, individual devices, etc.), select the feature or
device to be disabled, and then press the jog dial to confirm the disablement.
5. Press F2 (Exit) to exit the menu.
Repeat to enable a disabled feature or device.
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......