Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
127
Loop Class configuration
Select Loop Class to configure the installation loop Class (Class A or Class B).
The default setting is Class A.
To configure a loop as Class A or Class B:
1. Select Field setup in Main menu.
2. Select Loop Class and select the loop number (1 for one-loop panel; 1 or 2 for
two-loop panel, etc.).
3. Select Class A or Class B.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Remote disable/enable configuration
Use the Disable/Enable menu to remotely disable and enable system features
and devices in a fire network. Disabled features and devices do not indicate
faults or fire alarms.
If remotely disabling zones in alarm, you must reset the control panel associated
with the zone in alarm to complete the operation.
Remotely disabling or enabling a system feature or device
To remotely disable a feature or device:
1. Select Remote Disable/Enable from the Main menu, and then select Remote
disable.
2. Select Panel, and then select ALL or Firenet ID to define the scope of the
remote disable/enable command (all panels in the network or a single panel
in the network).
3. Select Element, and then select Zone, Device, Group, or Panel.
Enter the zone number, address, or ID for the element that you want to
disable or enable. See Table 67 on page 128 for more information.
If the zone, address, or ID entered doesn’t exist, no action is taken.
4. Select Channel.
Enter the channel, if required. See Table 67 on page 128 for more information
5. Select Active, and then select NO (to disable a feature or device) or YES (to
enable a previously disabled feature or device).
6. Press F4 (Enter), and then press F1 (Back).
7. Press F2 (Exit).
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......