Chapter 3: Configuration and commissioning
128
ZP2-A Series Installation Manual
Table 67: Remote disable/enable – configuring Element types
Element
Description
Zone [1]
Remotely disables or enables a zone. Enter the zone number (for
example, 0001).
Device
Remotely disables or enables a device. Enter the loop number and
the device address (for example, 1.001).
Group
Remotely disables or enables an output group. Enter the output
group number (for example, 001).
Panel
Remotely disables or enables the ZP1-X3E extinguishing panel with
the Firenet ID entered in step 2.
[1] For control panels in regional mode VdS 2540, enter the zone number and the point number
(for example, 0001/01).
Table 68: Remote disable/enable – configuring Channel data
Channel
Description
---
Devices with only a single input or output (detectors, manual call
points, sounders). This is the default setting.
I1, I2, I3, I4
Inputs 1 to 4 for I/O modules.
O1, O2, O3, O4
Outputs 1 to 4 for I/O modules.
BS
Sounder channel for sounder bases when the sounder base and the
detector use a single device address (the detector channel is ---)