P/N 501-415603-4-20 • REV 2.0 • ISS 06JUL11 

 

ZP1-F Series Quick Installation Guide 

Figure 1: Zone and device connections 

 

 

Overview 

This document provides quick installation information for 
your product. For detailed installation information, 
including EN 54-13, intrinsically safe, and BS 5839-1 
operating mode requirements, see the installation 
manual. 

Zones and zone devices 

Connect zone wires and devices as shown in Figure 1. 

Line resistance 

Mixed zones 

40 

 max. 

Automatic / manual zones 

55 

 max. 

Detectors and manual call points per zone 

[1]

 

Ziton Z600 series detectors  32 max. 

EST E6 series 

32 max. 

Other detectors 

32 max. 

Manual call points 

32 max. 

[1] Or quantities defined by local codes and standards 

Manual call point resistance

 [1]

 

Mixed zone 

100 

 

Manual zone 

100 to 680 

 

[1] Resistance must be rated at 1 W min. 

Inputs and outputs 

The function of inputs and outputs is defined by the 
operating mode. 

Inputs 

EN 54-2 

Remote reset 

Delays off 

EN 54-2 Evacuation 

Remote reset 

Delays off 

EN 54-2 Scandinavia 

Fire routing / extended fire 
routing delay [1] 

Delays off 

BS 5839-1 

Class change 

Delays off 

NBN S21-100 

Remote reset 

Delays off 

NEN 2535 

Fire routing inhibit delay 

Delays off 

[1] Four- and eight-zone control panels only. 

Input circuits should have a maximum resistance of 
100 

 (including any cable resistance). 

Sounder outputs 

EN 54-2 

OUT1, OUT2, and OUT3 

EN 54-2 Evacuation 

OUT1, OUT2, OUT3, and OUT4 

EN 54-2 Scandinavia 

OUT1, OUT2, and OUT3 

BS 5839-1 

OUT1, OUT2, OUT3, and OUT4 

NBN S21-100 

OUT1 and OUT2 (Evacuation sounders) 
OUT3 and OUT4 (Warning sounders) 

NEN 2535 

OUT1 and OUT2 