background image

804053UK CS Res Quick Start Guide June 2016 - V3.01

Command-Centre

TM

 installation

CO

2

 Cylinder

Example HydroTap

®

G4 Classic model

    Arc  /  Cube             

Elite

Classic

Step 4-

 Installing the Command-Centre

TM

. Also refer to 803341UK Tap installation instructions 

(for Arc / Cube also refer to the tube kit assembly instructions) supplied with the tap.

GAS IN

WHITE

POWER

CABLE

USB

MAINS IN

SPARKLING 

OUTLET

CO2

IN

BLUE

CHILLED 

OUTLET

BRAIDED

Cold isolation valve

(not supplied)

Clearance 

Envelope

535mm

Note

 All plastic / silicon tubes must be trimmed to size. They must have a constant 

fall to the Command-Centre

TM

.

Note 

Mains hose length is 750mm.

Electrical power cable length is 3.0m nom.

Position the Command-Centre

TM

 according to the hose and cable lengths supplied.

280mm

50mm

50mm

Braided hose fitting

Install the mains water braided hoses to the Command-Centre

TM

 before locating in place.

Note

 Neither the braided hoses or the tubes supplied can be lengthened.  

 

Note 

Chilled and sparkling outlet tubes must be insulated with the foam insulation 

provided.

Commissioning

OPEN Position

CLOSED Position

ON

OFF

Stop cock

operation

Have a bucket or similar container (not 

supplied) at the ready to hold a 

quantity of water that will be ejected 

while the filter flush mode is in 

operation. Open the filter access 

door on the front of the Command-

Centre

TM

 and the filter cartridge will 

be exposed. Located to the rear right 

hand side of the cartridge is a flush 

line, approx 600mm long, and the 

flush line stop cock. Place the free 

end of the flush line into the bucket 

or container (not supplied).    

 Note 

At first commissioning, the system will select filter flush screen

 automatically.

• 

Press the [MENU] button for main menu.

• 

Press the [Install] button. 

• 

Press the [Purge CO] button. 

• 

In the next screen, press the [START] button 

to commence the purging process. 

• 

You will hear the CO

2

 gas running through 

the tap.

• 

Run for 10 seconds to fully purge the CO

2.

• 

Press the STOP button to stop the purge.

• 

Press [NEXT] for filter flush screen.

CO

2

 Purge

  Step 5-

 

Commissioning.

• 

Open the flush line stop cock.

• 

Press [START] button to start filter flush. 

• 

Allow at least 10 litres of water to flush 

through the filter.

• 

Once the filter flush is finished, close the 

flush line stop cock, then press [STOP] to 

end filter flush mode. 

Filter flush

The HydroTap

®

G4 is now ready to be commissioned. 

• 

Turn on the power, gas and water and check for any leaks.

• 

Familiarise yourself with the operation of the HydroTap

®

G4 in preparation 

for use (see User manual).

• 

Follow the installation instructions below (and review section C of the User 

manual). 

• 

Initially you will be prompted to select the language.

• 

After commissioning, the system may be customised by selecting further 

options in section G - Settings, of the User manual.

WARNING!

 

The cylinder ( containing 1kg of CO

2

 ) should be installed in a 

well ventilated area of area no less than 38m

3

.

If more than 1 gas cylinder containing 1kg of CO

2

 is present within the same 

location, the recommended ventilation area should be in proportion to the 

number of gas cylinders stored in that location.

A ventilated area in a non-enclosed area which could include the kitchen, living room etc.

See gas cylinder and MSDS sheet for complete list of warnings.

Secure the cylinder

Secure the gas cylinder supplied to a suitable wall, within 1 metre of the Command-

Centre

TM

, in an upright position. This is undertaken by screwing the metal bar holding the 

Velcro strap to a cupboard wall, 200mm above the floor or base of the cupboard. Make 

sure the gas cylinder can stand in place before securing to the wall. Due to regulatory 

requirements the gas cylinder must be stored securely and in an upright position. 

Connect the regulator

Remove the gas cylinder from the strap. Make sure the regulator knob is turned fully 

anti-clockwise to the end-stop before fitting. Screw on the regulator (clockwise). Be aware 

that some CO

2

 may be discharged from the connection to the regulator as the cylinder 

and the regulator are be assembled together. Any CO

2

 released will be cold. Screw on the 

regulator to stop this leakage. 

Note

 the leaking CO

2

 will be cold.

Note

 Two plastic seals are supplied with a new regulator. Only one is required, the other 

is supplied as a spare part. 

Connect the gas hose 

Connect the threaded end of the braided gas hose to the regulator, then connect the push 

fit fitting to the top of the Command-Centre

TM

 via  connection marked ‘CO

2

 IN’ .

To turn the gas on, rotate the black knob on top of the cylinder clockwise. Then adjust the 

outlet pressure, by rotating the regulator knob clockwise to between 2.7- 3.0 bar (green 

zone). 

Note

 

The arrow should sit in the green zone of the regulator gauge; it should not fall in 

the red or yellow zones. 

CO

2

 Regulator

ON - OFF knob

Note

 

When removing hose, take 

care not to lose plastic olive from 

the fitting.

Green indicator

Leak test

Faulty seal joint

Good seal joint

After replacing a cylinder or after making 

a gas connection, perform a leak test
Stage 1

• 

Turn the gas off.

• 

Using soapy water applied with a sponge, or with a 
brush, cover all of the  gas joints with a liberal amount 
of suds. 

Stage 2

• 

Turn the gas on.

• 

Adjust the pressure to between 2.7- 3.0 bar.

• 

Inspect the joints for leaks.

• 

If any bubbles appear to grow, the joint will need 
to be resealed and tested again. 

Reviews: