6.  Setting Transmission Interval for STH-03ZB 

6.1 

If necessary, remove STH-03ZB from mounting cradle (see 

"

Installing Mounting for 

STH-03ZB

""""

 section).

 

6.2  Using the following setting positions to set the appropriate transmission interval for 

STH-03ZB: 

Transmit Interval 

DIP Switch Setting  Transmit Interval 

DIP Switch Setting 

1 Second 

1 Minute 

5 Seconds 

5 Minutes 

10 Seconds 

10 Minutes 

15 Seconds 

15 Minutes 

20 Seconds 

20 Minutes 

25 Seconds 

25 Minutes 

30 Seconds 

30 Minutes 

35 Seconds 

35 Minutes 

40 Seconds 

40 Minutes 

45 Seconds 

45 Minutes 

50 Seconds 

50 Minutes 

55 Seconds 

55 Minutes 

60 Seconds 

60 Minutes 

65 Seconds 

65 Minutes 

70 Seconds 

70 Minutes 

75 Seconds 

 

75 Minutes 

 

6.3  Ensure STH-03ZB is connected to a coordinator device (see 

"

Adding STH-03ZB to 

Receiving Device

""""

 section). 

6.4  Use QuickView Data PS software on PC with coordinator device to confirm STH-03ZB 

transmissions are being received and the update interval has been set correctly. 

6.5  Replace STH-03ZB into mounting cradle (see 

"

Installing Mounting for STH-03ZB

""""

 section) 

as required. 

6.6  Transmission interval setting has been successfully configured. 

 

STH-03ZB User's Manual 

7.  Adding STH-03ZB to Receiving Device 

You will need: 

Sharp pointed tool 

Coordinator or router device (WZB-01USBPS or WZB-02485RPS or WZB-01USBPSR or 

WZB-05ETPS) 

 

7.1. Ensure coordinator or router device is powered on (see relevant device’s manual). 

7.2. Ensure batteries have been installed in STH-03ZB (see "

Installing and Replacing 

Batteries in STH-03ZB"

 section). 

7.3. Use the sharp pointed tool to apply 1 quick press to link switch on the coordinator or router 

device, the blue ZigBee LED should flash 1 flash per 0.5 second and repeat the sequence, 

detection can take up to 30 seconds. 

7.4. If 30 seconds has passed and no device has been connected, the blue ZigBee LED on the 

coordinator or router should return to one flash then pause for a second and repeat the 

sequence. 

7.5. When STH-03ZB has been connected, the blue ZigBee LED on the coordinator or router 

device should flash, it should return to one flash then pause for a second and repeat the 

sequence. 

7.6. If STH-03ZB has been successfully connected, the green status LED should flash every 60 

seconds to confirm successful addition. 

 

If STH-03ZB’s status LED does not flash once every 60 seconds, then it has not been connected 

successfully.    Repeat above steps until STH-03ZB has been connected successfully.    If 

STH-03ZB has still not been connected successfully after a few attempts, check it is within the 

operational distance of 50m (line of sight) from the coordinator or router device and away from 

other 2.4GHz devices that might interfere with its operation. 

 

If STH-03ZB had been successfully connected, but is showing unable to find coordinator or 

router device (repeating sequence of 2 flashes and pause for 2 seconds), then check coordinator 

and all router (where applicable) devices are correctly powered on.    If coordinator and all router 

(where applicable) devices are functioning correctly, STH-03ZB may be out of range from the 

coordinator or router device, an additional router may need to be added to extend the range. 

 

 

STH-03ZB User's Manual 

8.  Removing STH-03ZB from Receiving Device 

You will need: 

Sharp pointed tool 

 

8.1. Ensure coordinator or router device is powered on (see relevant device’s manual). 

8.2. Ensure STH-03ZB is powered on (see 

Installing and Replacing Batteries in STH-03ZB

 

section) and has already been connected to the coordinator or router device. 

8.3. Use the sharp pointed tool to apply 2 quick presses to the link switch on the coordinator or 

router device, the blue ZigBee LED should flash rapidly for up to 30 seconds or until removal 

has been successful, removal need to take place within 30 seconds. 

8.4. 3 quick presses to the link switch on STH-03ZB, the green status LED should flash rapidly 

for up to 30 seconds or until removal has been successful. 

8.5. If STH-03ZB has been successfully removed, coordinator or router device’s blue Zigbee 

LED should flash once and pause for one second then repeat the sequence, STH-03ZB’s 

green status LED should flash once per second. 

 

Recommendation:

 It is strongly recommended to remove batteries immediately from STH-03ZB 

once it has been removed successfully from the coordinator or router device as this will greatly 

improve battery life. 

 

9.  STH-03ZB LED Signal Status 

The table below shows the LED signal status for STH-03ZB: 

STH-03ZB LED 

Status 

Green LED:   

1 flash per second (loop) 

Ready to join

 – ready to be connected to 

coordinator or router 

Green LED:   

1 flash every 60 seconds (loop) 

Successfully Connected

 – connected and 

functioning normally 

Green LED:   

Rapid flashing (continue) 

Orphaned

 – connected but unable to find 

coordinator or router 

Green LED:   

Rapid flashing up to 30 seconds 

Removing

 – being removed from coordinator or 

router 

Green & Red LED:   

ON for 3 seconds 

ZigBee Reset

 – Zigbee linkage to all data 

receivers being reset

 

Red LED: 

1 flash every 60 seconds (loop) 

Low Power

 – low battery power, replace 

batteries immediately

 

 

 

STH-03ZB User's Manual 

10. ZigBee Reset 

In the case where the data receivers (coordinator or router devices) for the STH-03ZB are no 

longer available or have been reset, to clear STH-03ZB ZigBee linkage to all data receivers, 

apply 3-second press to the link switch,

 

the green and red status LEDs should be ON for 3 

seconds, then return to just the green status LED flashing once every 1 second. 

 

STH-03ZB’s ZigBee linkage to all data receivers has been cleared. 

 

Recommendation:

 It is strongly recommended to remove batteries immediately from STH-03ZB 

once its linkage to data receivers has been removed successfully as this will greatly improve 

battery life. 

11. Product Specifications 

 

Measurement Channel 

Built-in 1 temperature and humidity sensor 

Wireless Protocol l 

Compliant IEEE 802.15.4, ZigBee2007/PRO 

Operating Frequency 

2.4GHz ISM Band 

Transmission Range   

50m (around 164 feet) Line of sight 

RF Output Power 

1mW/ 0dBm 

Power Supply 

3V 2 AA    Alkaline battery   

Operating Environment 

-10~ +55 ºC, 85%RH. Max. 

Power Consumption 

TX:35mA    Sleep:1.3uA 

Measurement Accuracy 

Tempe0.5 ºC/ Hu/-5% 

Network Topology 

Star/ Tree/ Mesh 

Transmitting protocol 

Modbus RTU 

Addressing 

IEEE MAC 64bit 

Transmit Interval 

1 second to 75 minutes setting by DIP Switch   

Battery Life 

1 year based on sending data per 5 minutes 

Coordinator    WZB-01USBPS / WZB-05ETPS 

Peripherals 

Router 

WZB-01USBPSR / WZB-02485RPS 

Dimensions 

92(L) x 50(W) x 23(H) mm 

Weight 

86g 

OS   

Windows 95/ 98/ NT/ 2000/ XP/ Vista/ Win7 

Certifications 

CE/ FCC 

 