Default settings of the programs
15.1 VDE-AR-N 4105:2011+2018
When changing the program, all parameters are reset.
Germany VDE-AR-N4105:
Generator, Pn
2011
2018
≤ 50 kW > 50 kW
3AC +
3AC +
3AC +
3AC +
My
3AC+N
1AC+N
3AC+N
3AC+N 3AC+N
Data
230 V
230 V
230 V
230 V
230 V
Main
Sub
Parameter
Pr1.01
Pr1.07
Pr1.02
Pr1.08
Pr1.09
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ver. 00
Ma
ins
con
n
ec
-
tion
Connection
3AC-N /
3AC
1AC-N
3AC-N /
3AC
3AC-N /
3AC
3AC-N /
3AC
Nominal voltage [V]
230,0
230,0
230,0
230,0
230,0
Coupling device
no
no
no
no
no
S
w
it
ch o
n
con
d
it
ion
s
Voltage
Active
no
no
no
no
no
U max.
[V]
259,0
259,0
252,5
252,5
252,5
U min.
[V]
189,0
189,0
196,0
196,0
196,0
Frequency Active
no
no
no
no
no
F max.
[Hz]
50,05
50,05
50,10
50,10
50,10
F min.
[Hz]
48,50
48,50
47,60
47,60
47,60
Switch on
delay
Time
[s]
60
60
60
60
60
After
alarms
Switch back
triggered triggered triggered triggered triggered
Short alarm Active
yes
yes
V
o
lt
age
U >>
Alarm active
yes
yes
yes
59.S2
Alarm on
[V]
287,5
264,5
287,5
59>S2
Alarm off
[V]
252,5
252,5
252,5
Delay alarm on [s]
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
U >
Alarm active
yes
yes
no
no
no
59.S1
Alarm on
[V]
264,0
264,0
264,0
264,0
264,0
59>S1
Alarm off
[V]
259,0
259,0
252,0
252,0
252,0
Delay alarm on [s]
0,10
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
60
UM>
Alarm active
yes
yes
yes
yes
yes
59-Av
Alarm on
[V]
253,0
253,0
253,0
253,0
253,0
Alarm off
[V]
250,0
250,0
248,0
248,0
248,0
Delay alarm on [s]
0,10
0,10
0,10
0,10
0,10
Delay alarm off [s]
60
60
60
60
60
U <
Alarm active
yes
yes
yes
yes
yes
27.S1
Alarm on
[V]
184,0
184,0
184,0
184,0
184,0
27<S1
Alarm off
[V]
189,0
189,0
196,0
196,0
196,0
Delay alarm on [s]
0,10
0,10
3,00
0,10
1,00
Delay alarm off [s]
60
60
60
60
60
U <<
Alarm active
yes
no
yes
27.S2
Alarm on
[V]
103,5
103,5
103,5
27<S2
Alarm off
[V]
196,5
196,5
196,5
Delay alarm on [s]
0,30
0,30
0,30
Delay alarm off [s]
60
60
60
Pr1.02:
- set ex works
Pr1.02, Pr1.08, Pr1.09:
- Code lock ex works activated
- Blue values -> parameters that can be changed with code lock
Grey values can only be read (not changed) regardless of the code lock/sealing.
pre-set at
factory