background image

 

STW20K 

12440-0702-03

 

Page

 

7 / 8 

www.ziehl.de 

  

12 

Technical data 

 

Rated supply voltage Us 

DC/AC 24 

– 240 V 0/50/60 Hz 

Tolerance 

DC 20.4 - 297 V  AC 20 - 264 V  45 -62 Hz 

Power consumption 

< 1 W 

< 4 VA 

 

Input 

 

Transformer 

1-3 STWA1 or STWA1H 

Rated thermal continuous current Icth 

AC 100 A 

Thermal rated short-time current Ith 

AC 300 A for 10 s 

 

Limits 

 

operating mode 

On, Off 

Switching threshold on 

Ion ≥ AC 1 A 

Switching threshold Off 

Ion ≤ AC 0.4 A 

tolerance 

± 20 % 

delay 

< 300 ms 

Off delay 

< 300 ms 

 

Output relay K1, K2 (Alarm 1, 2) 

2 x 1 change over contact 

Switching voltage 

max. AC 300 V; DC 300 V 

 

min. voltage / current 

12 V 10 mA 

 

conventional thermal current Ith 

max. 5 A    

 

Switching power 

max. AC cos φ = 1 

1250 VA    250 V * 5 A 

Utilization category  
Rated operational current 

AC-15  Ie = 3 A Ue = 250 V 

Rated operational voltage  

DC-13  Ie = 2 A Ue = 24 V  
DC-13  Ie = 0.4 A Ue = 120 V; Ie = 0.2 A Ue = 240 V 

Recommended fuse NO 

4 A time-lag or miniature circuit-breaker MCB B4 

Recommended fuse NC 

3,15 A time-lag 

 

 

 

Test conditions 

EN 61010-1 

Rated impulse voltage 

4000 V 

Overvoltage category 

III 

Pollution degree 

Rated insulation voltage Ui 

300 V 

On-period 

100 % 

 

EMC-tests 

EN 61326-1 industrial environment 

Emission 

EN 61326-1; CISPR 11 Class B 

Immunity 

EN 61326-1 

Electrical fast transient/burst 

EN 61000-4-4 ±4.5 kV 

 

Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms 

Surge immunity 

IEC 61000-4-5 ±1 kV 

 
 

Installation conditions 

 

Permissible ambient temperature 

-20 °C ... +65 °C 

Permissible storage temperature 

-

20 °C …+70 °C 

Installation height 

< 2000 m over N.N. 

Climatic conditions 

5-85% rel. F., no condensation 

Permissible wiring temperature 

-

5 °C …+70 °C 

Vibration resistance EN 60068-2-6 

2 … 13.2 Hz ±1 mm   13.2 ... 100 Hz 1 g 

 

2…25 Hz ±1.6 mm    25 ... 150 Hz 5 g 

Summary of Contents for STW20K

Page 1: ...w ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual STW20K updated 2019 07 31 Fu STW20K 12440 0702 03 Page 1 8 www ziehl de Current Relay for AC Detection AND Evaluation 3 Transformers ...

Page 2: ...2 Display and controls 3 3 Application and short description 3 4 Overview of functions 3 5 Connecting diagram 4 6 Important Information 4 7 Installation 5 8 Commissioning 5 9 Detailed description 6 9 1 Tips 6 10 Disposal 6 11 Error search 6 12 Technical data 7 13 Housing Type K 8 ...

Page 3: ...ent in up to 3 lines with current transformers STWA1 AND circuit If there is a current in all 3 monitored lines the relay 2 change over contacts picks up If there is no current in at least one of the lines the relay releases The relay works in closed circuit current When voltage is applied to the STW the relay signals an alarm until the it has picked up Identifies power failure with 1 or 3 phase e...

Page 4: ...d the relevant security instructions for the setting up and the use of electrical units The equipment is built according to EN and checked and leave the plant according to security in perfect condition If in any case the information in the instructions manual is not sufficient please contact our company or the responsible representative To maintain this condition you must observe the safety instru...

Page 5: ...se twisted or shielded cables Attention The polarity of the current transformer output white marking on the cable must be observed only if several current transformers are connected in series to increase the sensitivity 7 Installation mount on 35 mm mounting rail according to EN 60715 wall mount with 3 x screws M4 connecting wires refer to the connection plan to prevent miss operation and malfunct...

Page 6: ...t too high current in wire too low Loop through wire several times Limit too low small loads shall not be recognized Connect a resistor 0 25 W 200 V in parallel to the current transformer STWA1 H resistor 750 Ohm enhancement by factor 2x resistor 330 Ohm enhancement by factor 4x resistor 150 Ohm enhancement by factor 10x Because of high tolerances we recommend to determine the best value by try ou...

Page 7: ...current AC 15 Ie 3 A Ue 250 V Rated operational voltage DC 13 Ie 2 A Ue 24 V DC 13 Ie 0 4 A Ue 120 V Ie 0 2 A Ue 240 V Recommended fuse NO 4 A time lag or miniature circuit breaker MCB B4 Recommended fuse NC 3 15 A time lag Test conditions EN 61010 1 Rated impulse voltage 4000 V Overvoltage category III Pollution degree 2 Rated insulation voltage Ui 300 V On period 100 EMC tests EN 61326 1 industr...

Page 8: ... AWG 22 14 Stranded wire with ferrules insulated ferrules 1 x 0 14 mm2 1 5 mm2 AWG 28 16 Stripping length Tightening Torque 8 mm 0 5 Nm Protection class housing terminals IP40 IP 20 Mounting Snap mounting on 35 mm standard rail EN60715 or M4 screws additional bar not included Mounting position any Weight app 120 g Subject to technical changes 13 Housing Type K 1 Bottom 2 Top 3 Bolt 4 Screw 5 Holes...