9  Trouble – shooting and remedies 

Relay does not turn on: 

  check that the control voltage at terminals A1, A2 is correctly applied and corresponds to the 

device voltage specified on the device's rating plate. 

  check that the current transformer is properly connected. The consumer must be turned on. 

Verify that only one conductor is routed through the transmitter. 

 
 
 

10  Technical data 

Control voltage Us: 

 

Refer to the unit rating plate 

Tolerance 

DC 21 - 30 V 

AC -15 - +10%; 50/60 Hz 

Power consumption 

< 1.5 W 

                   < 2 VA 

 

Relay outputs K1, K2 (Alarm 1, 2) 

1 switching contact 

Switching voltage 

max AC 415 V 

Conventional thermal current Ith 

max 6A 

Switching capacity max AC cos φ = 1 

2000 VA (resistive load) 120W at 24 V 
DC 

Electrical contact life cos φ = 1 

1 x 10 

5

 switching cycles at 240 V / 6 A 

Durability of mechanical contact 

3 x 10

 7

 switching cycles 

Short circuit resistance (NO) 
Short circuit resistance (NC) 

4 A slow action or LS switch 
B4 3.15 A slow action 

Shutdown capability  
Category  

AC-15 Ie = 3 A Ue = 250 V 

Rated operational current 
Rated operational voltage 

DC-13 Ie = 2 A Ue = 24 V 

Reduction factor for cos φ = 0.3

 

0.5 

 

Transformer connection 

 

Connection transformers 

1 … 8 pcs Type STWA1 or STWA1H 

Alternating current - internal resistance 

approx. 7kΩ 

Transformer overload capacity 

max 100A continuous, max 300 A for 10 s 

 

Switching points 

 

Switching value 

app. AC 1 A 

       Activation delay 

< 200 ms 

      Switch-off delay 

See nameplate (without < 200 ms) 

 

Testing conditions 

EN 61010-1 

Rated withstand voltage 

4000V 

Overvoltage category 

III 

Degree of contamination 

Rated insulation voltage Ui 

250V 

On-time 

100% 
 

EMC tests 

EN 61326-1 

Interference emission 

EN 61326-1; CISPR 11 Class B 

Interference immunity 

EN 61326-1 (industrial environment) 

 
 

 

Summary of Contents for STW1K

Page 1: ...uring Transducers Grid and Plant Protection Operating Manual STW1K updated 2022 07 13 Um For more information and help about this product please scan the QR Code or choose the following link STW1K Operating manual Quick guide Datasheet Connection diagram CAD Data Firmwareupdates FAQ Videos about installation and settings Certificates STW1K 10630 0710 00 page 1 6 www ziehl de AC Current Sensing Rel...

Page 2: ...ensure the functionality and safety of the product If the following instructions given especially but not limited for general safety transport storage mounting operating conditions commissioning and disposal recycling are not observed the product may not operate safely and may cause a hazard to the life and limb of users and third parties Deviations from the following requirements may therefore le...

Page 3: ...g for a central extraction system in wood processing 3 Functional overview 8 inputs in OR circuit relay on when 1 input is activated response threshold approx 1 A connection of current sensor S1 power supply for S1 required switch off delay approx 10 s Inputs that are not required remain open 4 Wiring scheme 5 Important notes DANGER Hazardous voltage Will cause death or serious injury Turn off and...

Page 4: ...ctor 2 330 Ω resistor increase by a factor 4 120 Ω resistor increase by a factor 10 Due to large tolerances that must be considered we recommend that the best values be determined by trial and error method Length of connecting cables STWA1 H Up to 50 m also much longer are also possible Shielding may be required when laid parallel to power lines 7 Assembly The unit can be mounted as follows mounti...

Page 5: ... 1 1 x 10 5 switching cycles at 240 V 6 A Durability of mechanical contact 3 x 10 7 switching cycles Short circuit resistance NO Short circuit resistance NC 4 A slow action or LS switch B4 3 15 A slow action Shutdown capability Category AC 15 Ie 3 A Ue 250 V Rated operational current Rated operational voltage DC 13 Ie 2 A Ue 24 V Reduction factor for cos φ 0 3 0 5 Transformer connection Connection...

Page 6: ... Fine wire with conductor ferrule 1 x 0 14 mm 2 2 5 mm 2 AWG 28 16 Strip length tightening torque 8 mm 0 5 Nm Protection snaps IP40 IP 20 Fastening Snap on mounting on 35 mm mounting rail according to EN 60715 or screw fixing M 4 Mounting position any Weight approx 150 kg Subject to technical changes 11 Design K Dimensions in mm 12 Disposal Disposal should be carried out properly and in an environ...

Reviews: