ZIEHL STR100 Operating Manual Download Page 4

 

STR100 

10460-0703-00

 

Page

 

4 / 8 

www.ziehl.de 

  

Detailed Description 

The STR 100 measures the resistance of a Pt 100 RTD. The STR 100 monitors sensor line interruption and 
sensor short circuit. A red LED signals sensor failure. 
The  signal  is  send  to  both  independent  electronic  channels  and  compared  with  the  preset  limit.  Every 
comparator sets a relay. The relay contacts are made in series thus the outputs operate as a single change 
over contact. When temperature is below the preset limit and there is no failure in the sensor circuit both relays 
K1 and K2 can pick up and contact 11, 14 is closed. 
The red LED "Sensor" signals a failure in the sensor circuit and both relays release. Contact 11, 12 is closed 
for warning/alarm. The red LED K1 and LED K2 also signal alarm when temperature exceeds the preset limit 
and both relays K1 and K2 release. The green LED ON/Ready is not alight and control relay picks up, the 
contact at terminal 6,7 is open (break contact, nc). The STR 100 operates now in not changeable safety 
mode, the relays are locked. When temperature is app. 10 K below the limit the control relay (contacts 6/7 
close) releases and the green LED is alight. The STR 100 now operates in changeable safety mode, the 
relays can be reset manually with built-in reset button or with external contact (make contact, no) at terminal 
Y1, Y2. 
 

Function Chart 

 

Important Information 

 

DANGER! 
 Hazardous voltage! 
 Will cause death or serious injury. Turn off and lock out all power 
 supplying this device before working on this device. 

 

Before connecting the device to the mains voltage, make sure that the control 
Voltage Us on the type plate corresponds to the mains voltage connected 
To the device! 

 

To use the equipment flawless and safe, transport and store properly, install and start professionally and 
operate as directed. 
Only let persons work with the equipment who are familiar with installation, start and use and who have 
appropriate qualification corresponding to their function. They must observe the contents of the instructions 
manual, the information which are written on the equipment and the relevant security instructions for the 
setting up and the use of electrical units. 

R

G

A1/A2

11

12

14

T1/T2

Y1

Y2

LED

K1,K2

21

22

ON/Ready

!

!

LED

Sensor

LED

Shortcircuit

Summary of Contents for STR100

Page 1: ...ehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual STR100 updated 2020 06 25 sm STR100 10460 0703 00 Page 1 8 www ziehl de Safety Temperature Limiter Supply voltage AC230V Category 3 EN954 1 ...

Page 2: ...ating conditions commissioning and disposal recycling are not observed the product may not operate safely and may cause a hazard to the life and limb of users and third parties Deviations from the following requirements may therefore lead both to the loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation ...

Page 3: ...ding EN 60730 VDE 0631 The temperature is measured with a Pt 100 resistance temperature detector RTD according to EN 60751 IEC 751 The process qualification in combination with the sensor must be proved To fulfil affords for higher safety functionality the function has to be routine tested periodically The thermostat series STR 100 meets safety category 3 Safety of machines EN 954 1 TÜV Rheinland ...

Page 4: ...ys are locked When temperature is app 10 K below the limit the control relay contacts 6 7 close releases and the green LED is alight The STR 100 now operates in changeable safety mode the relays can be reset manually with built in reset button or with external contact make contact no at terminal Y1 Y2 6 Function Chart 7 Important Information DANGER Hazardous voltage Will cause death or serious inj...

Page 5: ... assembled with screws M4 Wiring directly to plug base connect wires as per wiring scheme Apply mains voltage to terminals A1 and A2 The lines of the sensor circuit are to be routed as separate control lines Observe the maximum admissible temperature when installing in a switchgear cabinet Make sure sufficient space to other equipment or heat sources If the cooling becomes more difficult e g throu...

Page 6: ... connection 2 wire Pt100 according EN60751 IEC751 0 00385 max current 3 15 mA 10 mA at 200 0 C max voltage 2 V open terminal 15 V Line compensation normally Standard 0 5 Ω Option up to max 30 Ω Release function Release Over temperature interruption short circuit and malfunction Temperature limit Adjustable see temperature range Accuracy 3 of scale Repeatability 1 Hysteresis 10 C 25 3 C at 200 0 C ...

Page 7: ... conditions Operating temperature 0 C 50 C EN 60068 2 2 dry heat Storage temperature 20 C 70 C Altitude 2000 m above sea level Vibration resistance 1 mm at 25 Hz 10 g 25 100 Hz Shock resistance 10 g for 20 ms 20 g for 4 ms Housing Construction type S12 Material housing PA 6 6 UL94 V 2 Material socket PA 6 6 GF25 UL94 HB Dimensions H x W x D 82 x 42 x 121 mm IP Code housing IP40 IP Code terminals I...

Page 8: ...e S12 13 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal provisions 104 5 82 36 23 5 5 41 5 80 34 1 2 3 4 5 6 7 8 9 10 11 12 82 41 5 17 7 5 5 11 5 17 5 5 10 14 27 5 41 16 38 61 116 5 3 2 1 1 ...

Reviews: