SPI1021  

12570-0701-07

  

Page

 

14 / 24 

www.ziehl.de 

  

9.5  Menu mode (last decimal point on) 

The menu mode is used to select the menu items. If no key is pressed for 30 s, one automatically returns to 
the display mode. 

Function button 
Set / Reset 

Press briefly: Change into the configuration mode 

Press for ≥ 2 s: Returns to the display mode (the most recently set  values 

are then applied) 

Function key  
Up / Down 

Press briefly: Select menu item; changes into the display mode 

 

9.6  Configuration mode

 

(last Decimal point flashes) 

In the configuration mode you can set the value of a parameter. The display alternates between the parameter 
relation and the currently set value until one of the Up/Down buttons is pressed, which changes the value of 
the parameter. If no key is pressed for 2 s the display starts alternating again. 
If no key is pressed for 30 s (simulation mode 15 min) one automatically returns to the display mode (the most 
recently set value is applied during this) 

Function button 
Set / Reset 

Press briefly: The settings are taken over; continue to next parameter. 

Changes into menu mode after the last parameter 

Press for ≥ 2 s: Returns to the display mode (the most recently set values are 

then applied) 

Function key  
Up / Down 

Press briefly/long: Value change of the parameter (slow/fast) 

 
Hint:    Simultaneously pressing the Up and Down keys resets the adjustable value to zero. If the Up or Down 

button is kept pressed while setting the value the change in the display is accelerated. 

 

9.7  Self-test execute

 

 

In programs 1, 3, 4 the SPI1021 has an automatic self-test as recommended in CEI 0-21 and DEWA.  
K1 can pick up only after the self-test has been passed once.  
Self-test starts automatically as soon as measuring voltage is connected for the first time to a new device and 
when there is no alarm! Self-test also starts automatically when program has been changed to 1, 3, 4. 
Self-

test can be started manually by pressing button Test for ≥2 s. 

During the Self-test is 

8

test

8

 displayed.  

At the end of the test the result 

8

pass

8

 (passed) or 

8

fail

8

 (not passed) is displayed for 30 seconds. Reset 

stops the test. 
During self-test supply- and measuring-voltage may not be disconnected! 
 

9.8  Display Self-test result

 

 

The values and times have been measured during self-test can be displayed by pressing button Test shortly.  
Kind of limit  (

8

U::

 

8

 , 

8

U: 

 

8

 , 

8

Um  

8

 , 

8

U_  

8

 , 

8

U__ 

8

 ,

 

8

f::

 

8

 ,

 8

f: 

 

8

 , 

8

F_  

8

8

F__ 

8

 ), response time, 

measured value, trigger value and adjusted limit are displayed. LEDs (yellow) at the 

terminals L1…N shows 

the measured and trigger value. 
By pressing Test shortly display changes to the values of the next kind of limit. At last the result  

8

pass

8

 (passed) 

or 

8

fail

8

 (not passed) is displayed and additionally the switching time from K1 if

 

8

trel

8

 

is activated. 

Display automatically returns to normal mode 30 s after button Test has been pressed for the last time.  
 

9.9  Alarm counter 

The alarm counter 

8

ac  

8

 is increased by 1 with every shut-down. Up to 100 shut-downs are counted. That 

allows quick detection of how often the SPI1021 has shut down since the last delete of the alarm counter (see 
cumulative alarm time).  
Query the alarm counter: 

  Change into the display mode

 

  Press the   button several times until 

 display 

8

ac

xx

8

 

 
 

 

Summary of Contents for SPI1021

Page 1: ...ng Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual SPI1021 updated 2018 03 08 Ba from Firmware 0 0 SPI1021 12570 0701 07 Page 1 24 www ziehl de Grid and Plant Protection According to CEI 0 21 and DEWA standard with self test for 11kW and Watchdog with integrated vector shift relay Pr3 default ...

Page 2: ...iption of the parameters 13 9 4 Display mode last decimal point off 13 9 5 Menu mode last decimal point on 14 9 6 Configuration mode last Decimal point flashes 14 9 7 Self test execute 14 9 8 Display Self test result 14 9 9 Alarm counter 14 9 10 Cumulative alarm time display in hours 15 9 11 Alarm Memory 15 9 12 Standby counter and standby time 15 9 13 Code lock 16 9 14 Sealing 16 9 15 Simulation ...

Page 3: ...ashes Configuration mode 7 Set Reset key in display mode normal state Press briefly Display of next measured value alarm counter Press for 2 s Reset quit error messages Press for 4 s Displays the program e g 8Pr 18 Press for 10 s Displays the software version e g 80 0 8 8 Up Down key in display mode normal state Press briefly Change to the menu mode display of alarm memory Down cumulative time of ...

Page 4: ... 17 5 10 5 10 5 17 5 4 3 dal Response time s 0 20 0 20 0 20 0 20 0 20 0 60 dof OFF delay s 0 0 0 0 0 0 UM 59 Av UM Alarm on off On On On On On On UM Overvoltage V 253 438 253 253 438 110 HM Hysteresis V 10 0 17 5 10 0 10 0 17 5 4 3 dal Response time s 3 00 3 00 3 00 3 00 3 00 3 00 dof OFF delay s 0 0 0 0 0 0 U_ 27 S1 27 S1 u_ Alarm on off On On On On On On u_ Undervoltage V 196 339 196 196 339 85 ...

Page 5: ...2 vsr Number of phases 3ph 3ph 3ph 3ph 3ph Rocf 81r rocf Alarm on off Off Off Off Off Off Off dfdt delta f delta t Hz s 0 800 0 800 0 800 2 000 2 000 2 000 Per periods 20 20 20 20 20 20 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 1 1 1 rEL trEL response time Y1 s 5 0 5 0 Off 5 0 5 0 5 0 Don Delay On s 300 300 300 300 300 300 Mode mode Mode Tran Tran Tran Tran Tran Tr...

Page 6: ...ice has been installed a self test starts automatically The self test can be repeated when required All values of the test are stored and can be read out at the display Monitoring of under and overvoltage 0 15 520 V Measuring of 3 phases with or without neutral or single phase Monitoring of over and underfrequency 45 65 Hz voltage dependent adjustable Monitoring of quality of voltage 10 minutes av...

Page 7: ...acts not connected set 8rel 8 8trel 8 8 off 8 2 Fuses only when line protection necessary e g 3x16A 3 8Pr 38 Phase connect to L1 L2 and L3 are not connected 4 N connected set 8Pr 18 8Pr 38 8Pr 48 5 NC or NO contacts can be connected automatic detection when switching on 6 must be connected for plants 20kW ...

Page 8: ... death bodily injury or property damage to the device itself and to other devices and equipment If the information contained in the operating instructions operating manual are not sufficient please contact us directly or contact your responsible agency or representative Instead of the industrial norms and stipulations stated in the operating manual and applicable in Europe you must comply with the...

Page 9: ...t value turn on time section switch under 8rel 8 8trel 8 can switch off if not connected or if external devices switches can activate the section switch 8off 8 U Supply output for digital outputs DC 15 35 V IN1 teledistacco RCR volt free contact closed K1 released 50 ms Standby mode 8stby 8 IN2 commando locale volt free contact transitory mode open 8F 8 8F__ 8 8 on 8 8F 8 8F_ 8 8 off 8 closed 8F 8...

Page 10: ...he alarm each stands in the 7 segment display Alternately the time difference current operating time tripping operating time is displayed how long ago the alarm triggered Cumulative alarm time 8tal 8 The cumulative alarm time TAL indicates how long the relay was switched off due to an alarm It is recorded with a resolution of 1 minute and only when the control voltage is applied Query In the displ...

Page 11: ... 400V DEWA 6 3 AC without N 100V DEWA default setting Adjustment process If present remove seal only authorized person Apply control supply voltage at A1 A2 Slightly lift the key cover and turn 180 Actuate the small blue button by firmly pressing the button cover LED starts flashing until the green LED is illuminated Sealing is deactivated Press button 1x display 8Info 8 Press button 5x display 8P...

Page 12: ...p Down simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err5 Internal control Err7 Contactor feedback contacts K1 Err8 Limit error Err9 Parameter error 1 1 3AC N 300V Display mode Configuration mode Menu mode ...

Page 13: ...ing the Enable input 8 28 8 208 VSR 8 VSR8 81 Ph8 a vector surge on one phase leads to an alarm 83 Ph8 a vector surge on all phases simultaneously leads to an alarm 81 Ph8 83 Ph8 Limit value 8dfdt8 ROCOF df dt limit value 8 0 108 8 5 008 Periods 8per 8 Measuring time ROCOF 4 sensitive 50 insensitive Response time 8per 8 Period duration 8dal 8 8 48 8 508 delay Display 8ddi 8 Interval during which t...

Page 14: ...programs 1 3 4 the SPI1021 has an automatic self test as recommended in CEI 0 21 and DEWA K1 can pick up only after the self test has been passed once Self test starts automatically as soon as measuring voltage is connected for the first time to a new device and when there is no alarm Self test also starts automatically when program has been changed to 1 3 4 Self test can be started manually by pr...

Page 15: ...ower has been turned off Query alarm memory Change into the display mode Press the button several times display 8acxx8 Press the button 1x display 8 x xx8 8 x xx8 tripping value or error no time that has passed in hours Press the button 1x go to next alarm The alarm memory is only deleted during a program change 9 12 Standby counter and standby time The standby counter 8stby8 is increased by 1 wit...

Page 16: ... Press the button 1x Code lock on display 8 on8 flashes three times Code lock off display 8 off 8 flashes three times Return to menu mode menu item code lock If there any problems with the code lock Pin forgotten the lock can be switched off and the pin can be reset to 504 by keeping the Set key pressed while switching on the mains until 8Code8 8 off8 appears in the display 9 14 Sealing All the se...

Page 17: ...west section switch is displayed Adjustment process Select the menu item with the buttons until display 8si 8 Press the button 1x display 8si 8 8u 8 Use the buttons to set the measurement factor for simulation o 8u 8 Voltage 10min mean value frequency last simulated value o 8f 8 Frequency voltage last simulated value o 8vsr 8 Vector shift Press the button 1x display 8 2308 selected measurement fac...

Page 18: ...F 8dfdt8 8 per8 Limit ROCOF response time in periods 4 sensitive 50 insensitive 8stby8 Standby mode standby time standby counter 8Deon8 Delay Enable On suppression time when switching on and after opening the enable input 81 ph 8 83 ph 8 Single phase three phase vector shift evaluation 8rel 8 8trel8 Relay Section switch turn on time 8 off8 no feedback contacts tdon8 Power Up delay runs once at pow...

Page 19: ...ent principle Real root mean square measurement both half waves Hysteresis Adjustable 1 0 99 9 V Measurement error with N 0 6 of the measurement value Measurement error without N 0 8 of the measurement value Display accuracy 100V 1 digit res 1 V 100V 1 digit res 0 1V Measurement function 3 phase with without N Response time Adjustable 0 05 15ms 120 0 s Reset time Adjustable 0 200ms 999 s Frequency...

Page 20: ... withstand voltage 4000 V Overvoltage category III Pollution degree 3 Rated insulation voltage Ui 300 V Operating time 100 Permissible ambient temperature 20 C 55 C EN 60 068 2 2 dry heat EMC noise immunity EN 61000 6 2 EMC noise emission EN 61000 6 3 Housing Construction form V6 Front to back size 55 mm Dimensions W x H x D 90 x 105 x 69 mm Wiring connection single strand each 1 x 4mm2 Finely str...

Page 21: ...heck the connection Check for broken section switch Do a reset interrupt control voltage for 5s 8Err88 appears in the display Hysteresis error Upper threshold value must be higher than the lower threshold value check the threshold values 8Err98 appears in the display Parameter error Reset to factory settings see Program setup A time expires in the display Always when an OFF delay time 8dof 8 is ru...

Page 22: ...3 Riegel bar for snap mounting 4 Plombierung max Ø 1 8 mm sealing max Ø 1 8 mm 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 mm 48 58 45 3 61 8 16 5 90 Option 105 98 116 70 1 2 5 6 7 3 69 4 ...

Page 23: ...SPI1021 12570 0701 07 Page 23 24 www ziehl de 14 Verification in conformity CEI 0 21 ...

Page 24: ...SPI1021 12570 0701 07 Page 24 24 www ziehl de 15 Verification in conformity DEWA ...