Temperature Relays and MINIKA® 

Mains Monitoring 

Digital Panelmeters MINIPAN® 

Switching Relays and Controls 

Measuring Transducers 

Grid- and Plant Protection 

 

Operating Manual S1 adjustable

 

updated: 2019-08-08/Fu 

 

 

 

 

S1 adjustable 

11800-0702-01 

Page

 

1 / 6 

www.ziehl.de 

- Detection of current flow in a conductor

 

 

 
 

 

 

Table of contents 

 

1

 

General Notes ......................................................................................................................................... 2

 

2

 

Display and controls .............................................................................................................................. 2

 

3

 

Application and short description ......................................................................................................... 2

 

4

 

Overview of functions ............................................................................................................................ 2

 

5

 

Connecting diagram ............................................................................................................................... 3

 

6

 

Detailed Description ............................................................................................................................... 3

 

7

 

Important Information ............................................................................................................................ 3

 

8

 

Installation .............................................................................................................................................. 4

 

9

 

Commissioning....................................................................................................................................... 4

 

10

 

Error search ............................................................................................................................................ 4

 

11

 

Technical data ........................................................................................................................................ 4

 

12

 

Disposal .................................................................................................................................................. 6

 

13

 

Housing Type S1 .................................................................................................................................... 6

 

 
 

 

Summary of Contents for S1 adjustable

Page 1: ...t Protection Operating Manual S1 adjustable updated 2019 08 08 Fu S1 adjustable 11800 0702 01 Page 1 6 www ziehl de Detection of current flow in a conductor Table of contents 1 General Notes 2 2 Display and controls 2 3 Application and short description 2 4 Overview of functions 2 5 Connecting diagram 3 6 Detailed Description 3 7 Important Information 3 8 Installation 4 9 Commissioning 4 10 Error ...

Page 2: ...ate I Limit adjusts 3 Application and short description Recording of welding currents mounting at ground wire for controlling dedusting plants in combination with ZIEHL controls type STW Recording the state of a consumer of electricity on or off or defective In general the current sensor S1 is used where the current flow is to be detected with the exact value of the current either known from the p...

Page 3: ...all power supplying this device before working on this device To use the equipment flawless and safe transport and store properly install and start professionally and operate as directed Only let persons work with the equipment who are familiar with installation start and use and who have appropriate qualification corresponding to their function They must observe the contents of the instructions m...

Page 4: ...om monitored cable is too high no current trough monitored cable or current too low supply voltage 24 V DC is missing Sensor misplaced put on the cable and in parallel Output does not switch off Check adjusted limit crosstalk from a current is a neighbouring conductor sensor is in a magnetic field output has internal short circuit defective 11 Technical data Rated supply voltage Us DC 24 V Toleran...

Page 5: ...ature range operation 0 C 50 C transport 25 C 55 C storage 25 C 55 C 70 C max 24 h Altitude Up to 2000 m NN climatic conditions environmental Class EN60721 3 3 3K3 Humidity Damp heat IEC60068 2 30 55 C and 93 r H Vibration Operation IEC 60255 21 1 IEC 60068 2 6 Class 2 Transport IEC 60255 21 1 IEC 60068 2 6 Class 1 Seismic IEC 60255 21 3 Class 1 Shock Operation IEC 60255 21 2 Class 2 Transport IEC...

Page 6: ...0702 01 Page 6 6 www ziehl de 1 5 11 82 92 102 16 5 3 2 12 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal provisions 13 Housing Type S1 Dimensions in mm ...