MU2000K
12600-0752-00
Page 5 / 8
www.ziehl.de
6.5 Scaling of range
•
Power off the device
•
Press Button [Down] and keep pressed
•
Power on the device, and keep pressed the button [Down]
After 5s flashes the green LED, release button [Down]
Parameterization „input type“ → LED ON flashes 1x
•
Select with button [Set] the input type
→ displayed by LED U (DC voltage),
LED AC + U (AC voltage), LED I (DC current), LED AC + I (AC current)
•
Press button [Down]
Parameterization „input zero point“ → LED ON flashes 2x
Connect a signal at the input corresponding to the zero point
•
Press button [Down] (store of value, green LED flashes 3 times quickly)
Parameterization „input full scale“ → LED ON flashes 3x
Connect a signal at the input corresponding to the full scale
•
Press button [Down] (store of value, green LED flashes 3 times quickly)
Parameterization „output“ → LED ON flashes 4x
•
Select with button [Set] the output range
o
LEDs (U + I) 1 x flash -> output 0 - 10 V / 0 - 20 mA
o
LEDs (U + I) 2 x flash -> output 2 - 10 V / 4 - 20 mA
•
Press button [Down]
End of parameterization, LED ON lights permanently