ZIEHL MU100U Operating Manual Download Page 5

 

MU100U 

10730-0701-00

 

Page

 

5 / 8 

www.ziehl.de 

  

Connection examples 

 

 

 

Commissioning 

The following in-

/ output ranges can be set with the two trimming potentiometers “Zero” and “Scale”. 

 

Input 

Output 

 

0…20 mA  

 

0…20 mA  

0...10 V 

Factory Setting 

0…10 V  

2...10 V 

4…20 mA 

0…20 mA  

0...10 V  
2...10 V 

4...20 mA 

Can be adjusted by the 

customer 

 
To ensure that the accuracy class 0.5 is maintained even after the customer has been readjusted, the 
measuring instrument used should be at least class 0.1. 
 

Adjustment examples 

1)  Input 

0…20 mA or 0…10 V 

Output 

4…20 mA or 2…10 V 

 
Zero point: with zero signal at the input (set 0 mA or 0 V or bridge input), adjust the current or voltage output 

with the potentiometer “Zero”. 

 

For current output 4…20 mA (terminals 6 and 7) adjust to 4.00 mA, 

 

For voltage output 2…10 V (terminals 8 and 7) adjust to 2.00 V. 

 
Full- scale: set the input to max. signal (20 mA or 10 V), adjust the current or voltage output with the 

potentiometer “Scale”. 

 

For current output 4…20 mA (terminals 6 and 7) adjust to 20.00 mA, 

 

For voltage output 2…10 V (terminals 8 and 7) adjust to 10.00 V. 

 
Check zero and Full- scale and repeat if necessary. 
 
2)  Input 

4

…20 mA or 2…10 V 

Output  0

…20 mA or 0…10 V 

 
Zero point: at the input (terminals 1 and 2) set current constant to 4.800 mA. Adjust the current or voltage 

output with the 

potentiometer “Zero”. 

Summary of Contents for MU100U

Page 1: ...ehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU100U updated 2018 11 09 sm MU100U 10730 0701 00 Page 1 8 www ziehl de Universal Transmitter Isolation Amplifier ...

Page 2: ...rt description 3 3 Overview of functions 3 4 Connecting diagram 3 5 Important Information 4 6 Installation 4 7 Connection examples 5 8 Commissioning 5 9 Adjustment examples 5 10 Error search 6 11 Technical data 6 12 Housing Type K 8 1 Display and controls Adjust Full scale Adjust Zero LED green in Operation ...

Page 3: ... eliminates these problems The universal supply voltage and various input and output signals in one device drastically simplify warehousing The universal transmitter MU100U can be connected to any supply voltage between 24 V and 240 V DC or AC voltage can be connected Input and output signals are galvanically isolated Signals DC 0 4 20 mA or 0 0 V can be connected to the inputs Current and voltage...

Page 4: ...ndition you must observe the safety instructions in this instruction manual titled Important Information Failure to follow the safety instructions may result in death personal injury or property damage to the equipment itself and other equipment and facilities Instead of the industrial norms and regulations written in this instruction manual valid for Europe you must observe out of their geographi...

Page 5: ...o point with zero signal at the input set 0 mA or 0 V or bridge input adjust the current or voltage output with the potentiometer Zero For current output 4 20 mA terminals 6 and 7 adjust to 4 00 mA For voltage output 2 10 V terminals 8 and 7 adjust to 2 00 V Full scale set the input to max signal 20 mA or 10 V adjust the current or voltage output with the potentiometer Scale For current output 4 2...

Page 6: ...ame time and can be loaded with their rated load The offset adjustment has an effect on both outputs but can optionally be optimized for one output only 11 Technical data Rated supply voltage Us DC AC 24 240 V 0 50 120Hz Tolerance DC 20 4 297 V AC 20 264 V Power consumption 3 W 5 VA Inputs Voltage or current with GND1 Voltage input DC 0 10 V Max permissible voltage DC 200 V Nominal input resistanc...

Page 7: ...tic conditions 5 85 rel humidity no condition Installation height 2000 m over N N Housing Type K Dimension H x W x D 75 x 22 5 x 110 mm Width 1 TE Line connection solid wire 1 x 0 5 mm2 2 5 mm2 AWG 22 14 Standard wire with insulated ferrules 1 x 0 14 mm2 1 5 mm2 AWG 28 16 Torque 0 5 Nm Protection class housing terminals IP40 IP 20 Mounting Snap mounting on 35 mm standard rail EN60715 or M4 screws ...

Page 8: ... Page 8 8 www ziehl de 12 Housing Type K Dimension in mm 1 lower part 2 upper part 3 bar 4 screw 5 holes for screw mount 19 8 19 8 35 4 22 5 75 0 82 5 110 0 1045 1940 19 45 19 60 19 45 19 60 4 2 100 5 5 0 2 1 3 4 3 1 3 2 5 ...

Reviews: