ZIEHL MSF220K Operating Manual Download Page 4

 

MSF220K 

12710-0701-01

 

Page

 

4 / 7 

www.ziehl.de 

  

table of function 

overload:   PTC > 3650 

Ω 

normal: 

PTC < 1600 

Ω 

∞/0:   

PTC = 

∞ Ω / PTC = 0 Ω  

 

-> Sensor error 

 

PTC-temperature sensor 

alarm relays 

alarm LEDs * 

PTC 1 (T0-T1)  PTC 2 (T0-T2) 

alarm 1 

alarm 2 

AL1 

AL2 

normal 

normal 

off (terminal 11-14) 

off 

 

 

overload 

normal 

on (terminal 11-12) 

off 

 

 

overload 

overload 

on (terminal 11-12) 

on (terminal 21-24) 

 

 

normal 

overload 

off (terminal 11-14) 

on (terminal 21-24) 

 

 

only at 

parameterization: “monitoring sensor error on “ 

∞/0 

*1

 

normal 

*1

 

on (terminal 11-12) 

off 

 

 

normal 

*1

 

∞/0 

*1

 

on (terminal 11-12) 

off 

 

 

overload 

*1

 

∞/0 

*1

 

on (terminal 11-12) 

on (terminal 21-24) 

 

 

∞/0 

*1

 

overload 

*1

 

on (terminal 11-12) 

on (terminal 21-24) 

 

 

∞/0 

*1

 

∞/0 

*1

 

on (terminal 11-12) 

off 

 

 

 

* ) LED: 

 

off 

  on 

 

flash 

 

Important notes 

 

 

 

WARNING! 

 

 

 

 

Dangerous electrical voltage 

 

 

 

Disconnect power before working on equipment. 

 

 

 

Read and understand these instructions before installing, operating or maintaining 

 

 

 

the equipment. 

 

To use the equipment flawless and safe, transport and store properly, install and start professionally 
and operate as directed. 
Only let persons work with the equipment who are familiar with installation, start-up and use and who 
have appropriate qualification corresponding to their function. They must observe the contents of the 
instruction manual, the information written on the equipment and the relevant security instructions 
for the setting up and the use of electrical units. 

 

 

 

 

Attention! 

 

 

 

Before switching on make sure that the operational voltage Us of the type- plate and 

 

 

 

the mains voltage are the same! Before switching on ensure, that the supply voltage 

 

 

 

Us written on the lateral type plate corresponds to the mains voltage!  

 

When installing the device into the switchgear cabinet, please observe the max. admissible 
temperature. Care for both, sufficient clearance to other devices or sources of heat or enough forced 
draught. If cooling is made more difficult, e.g. close devices with increased surface temperature or by 
handicap of airflow cooling, the permissible ambient temperature has to be reduced. 

 

  

 

 

In case of failure of supply voltage, the monitored unit is not protected any more. 

 

 

 

The operator must ensure, that a failure is detected, e.g. by monitoring Alarm 1 (K1) 

 

 

 

or by testing the unit regularly. 

 

Summary of Contents for MSF220K

Page 1: ...ing Transducers Grid and Plant Protection Operating Manual MSF220K updated 2022 11 30 dr from Firmware 0 00 For more information and help about this product please scan the QR Code or choose the follo...

Page 2: ...th to the loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation from the specifications 2 Application and...

Page 3: ...open Green LED Power is on When nominal response temperature of PTC 1 T1 is exceeded relay K1 releases and red LED Alarm 1 is on Relay K1 picks up again when temperature at sensor comes below switchin...

Page 4: ...as directed Only let persons work with the equipment who are familiar with installation start up and use and who have appropriate qualification corresponding to their function They must observe the co...

Page 5: ...links evenly after 5s Alarm 1 becomes active relay K1 off terminals 11 12 closed red LED AL1 on after 8s Alarm 2 becomes active relay K2 on terminals 21 24 closed red LED AL2 on release button Test to...

Page 6: ...0 V ac 1 10 hp 3 0 FLA C 300 PTC thermistor input T0 T1 T0 T2 acc DIN 44081 DIN 44082 Number 2 x 1 6 PTC thermistor in series Rated response temperature TFS 60 C 180 C Response tolerance 6 C Temperatu...

Page 7: ...end sleeves 1x 0 14 1 5 mm2 Insulation Strip length 8 mm Tightening torque 0 5 Nm UL 7 lb in Protection housing terminals EN 60529 IP 20 Fitting position any Fastening fixing standard rail 35 mm EN 60...