ZIEHL-ABEGG RAE-2G Operating Instructions Manual Download Page 1

RAE-2/4/7/9G

Transformer controls for voltage controllable 1 ~ motors
Connection for 5-level thermostat for automatic speed control

Operating Instructions

Keep for reference!

L-BAL-E283-GB 1928 Index 002

Part.-No. 

english

D

|

GB

|

DK

|

E

|

F

|

I

|

PL

|

RU

|

S

|

 

 www.ziehl

­

abegg.com

Summary of Contents for RAE-2G

Page 1: ...rols for voltage controllable 1 motors Connection for 5 level thermostat for automatic speed control Operating Instructions Keep for reference L BAL E283 GB 1928 Index 002 Part No english D GB DK E F...

Page 2: ...view 5 3 1 Function 5 3 2 Maintenance 5 3 3 Transport 6 3 4 Storage 6 3 5 Disposal recycling 6 4 Installation 6 4 1 General notes 6 4 2 Minimum space requirement 7 4 3 Mains connection 7 4 4 Motor con...

Page 3: ...e developments construction methods and technical data given are subject to alteration We do not accept any liability for possible errors or omissions in the information contained in data illustration...

Page 4: ...ng of the motor fan the appropriate instructions in the drive documentation must be observed Attention Even after switching off dangerous temperatures can still occur in and on the device Attention Au...

Page 5: ...nsformer control unit for speed control of voltage controlled 1 fans In conjunction with a 5 level thermostat the fan speed is automatically adjusted to one of 5 levels For operation with no minimum a...

Page 6: ...tart up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations e g EN 50110 EN 60204 IEC 364 The 5 electrical safety rules must be observed Cover...

Page 7: ...rance on all sides of at least 50 mm has to be maintained to the housing walls switch cabinet doors wiring ducts etc The same clearance applies to the installation of several devices next to each othe...

Page 8: ...do not have the required motor protection It is recommended that every fan is equipped with a separate motor protection unit e g type S ET10 5 Enclosure 5 1 Technical data Line voltage 1 230 V 15 10...

Page 9: ...230 V AC max 0 5 A 5 Do not exceed the rated current of the internal fuse SR146K03 06 09 2017 RAE 9G N L1 PE Netz Line 1 230 V 50 60 Hz L1 N M 1 U1 U2 PE 1 Motor ohne Thermostatschalter without therm...

Page 10: ...5 3 Dimensions mm RAE 2 4 7G RAE 9G Operating Instructions RAE 2 4 7 9G Enclosure L BAL E283 GB 1928 Index 002 Part No 10 11...

Page 11: ...6 504 info ziehl abegg de http www ziehl abegg de 5 5 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for con...