background image

Caution!

Make sure that the connectors for mains, relays and control are 

rmly seated before start-up.

FSDM12/17/25/32/39/46

1

Line
FSDM12/17 tightening torque protective earth connection (M4 Torx T20): 2 Nm / 17.7 Lb In
FSDM25/32/39/46 tightening torque protective earth connection (M5 Torx T25): 4 Nm / 35.5 Lb In

2

Indication relays

3

Connection internal cooling fan

4

Parameter interface  for ZAstick

5

Jumper 

E1

 for input signal

6

Modulation

7

Option add-onmodule

8

Jumper for motor protection by thermostats 

TB

 or thermistors 

TP

 (factory setting)

Connection data terminals mains connection

 

FSDM5/7.5/8.5

FSDM12/17

FSDM25/32/39/46

Stripping length

10 mm

8...9 mm

12...13 mm

Max. conductor cross-section solid

1.5 mm

2

4 mm

2

16 mm

2

Max. conductor cross-section 

exible

2.5 mm

2

4 mm

2

10 mm

2

Max. conductor cross-section 

exible with wire 

end ferrule

2.5 mm

2

2.5 mm

2

10 mm

2

Max. conductor cross-section 

exible with wire 

end ferrule and collar

2.5 mm

2

2.5 mm

2

10 mm

2

Max. conductor cross-section AWG

AWG 12

AWG 12

AWG 6

Operating Instructions 

PMIcontrol Basic-M

 

 model series FSDM5...46

Electrical installation

L-BAL-E300-GB 1905 Index 001

Part.-No. 

27/48

Summary of Contents for PMIcontrol Basic-M Series

Page 1: ...PMIcontrol Basic M FSDM5 46 Frequency inverter for mounting on 3 motors for fans Operating Instructions Keep for reference L BAL E300 GB 1905 Index 001 Part No english...

Page 2: ...5 4 4 Mounting on the motor 16 4 4 1 Procedure FSDM5 7 5 8 5 16 4 4 2 Procedure FSDM12 17 18 4 4 3 Procedure FSDM25 32 20 4 4 4 Procedure FSDM39 46 22 4 5 Cable inlet 24 4 6 Outdoor installation 24 4...

Page 3: ...p 35 6 1 Prerequisites for commissioning 35 7 Diagnostics Faults 36 7 1 Status Out with ash code 36 8 Enclosure 39 8 1 Technical data 39 8 1 1 Maximum loading dependent on switching frequency line vol...

Page 4: ...ing instructions together with the device It must be ensured that all persons that are to work on the device can refer to the operating instructions at any time Keep the operating instructions for con...

Page 5: ...its accessories must only be used in a awless condition and installed and operated in compliance with the assembly instructions and or operating instructions Operating out side the device s technical...

Page 6: ...arges can appear between the protective ground PE and the mains connection The protective earth is conducting high discharge currents dependent on the switching frequency current source voltage and mo...

Page 7: ...intended for one quadrantdrives Insulation system and ball bearing of the motor must be suitable for speed control by a frequency inverter Only suitable for drives with low set off torque e g fans or...

Page 8: ...mark of conformity 5 DATA MATRIX Code con rmation number 12 Output values Output voltage Output frequency Value overload protection motor current 6 Production code 7 Serial number 8 Part no Type key...

Page 9: ...must be observed and adhered to 3 6 Storage The device must be stored in its original packaging in a dry and weather proof room Avoid exposure to extreme heat and cold Avoid prolonged storage we recom...

Page 10: ...case of transport damage Do not allow drilling chips screws and other foreign bodies to reach the device interior Keep enough distance minimum 50 mm to ensure unobstructed cooling air feed as well as...

Page 11: ...minal compartment B Motor connection adapter C Serrated locking nuts M4 D Countersunk screw M5 x 20 E PE clamp F Holder for PE clamps FSDM12 17 A Cover terminal compartment B Motor connection adapter...

Page 12: ...M5 x 20 F PE clamp G Holder for PE clamps FSDM39 46 A Cover terminal compartment B Motor connection adapter C Serrated locking nuts M5 D Serrated locking nuts M4 E Countersunk screw M6 x 20 F PE clamp...

Page 13: ...inal box ange The holes must be drilled according to the available motor Part No 00167112 Universal adapter plate without holes for mounting on the terminal box ange The holes must be drilled accordin...

Page 14: ...drilled according to the available motor Part No 00167193 Universal adapter plate without holes for mounting on the terminal box ange The holes must be drilled according to the available motor Operat...

Page 15: ...the adapter if required 1 For extension of the motor winding length approx 70 mm cross section 6 mm 2 2 For extension of the motor winding length approx 140 mm cross section 1 5 mm 2 4 3 Tool list 1...

Page 16: ...uts M4 3 Studs for fastening holder of the two PE clamps with 2 x serrated locking nuts M4 4 Studs for fastening cover terminal compartment with 5 x serrated locking nuts M5 5 Insert nuts for fastenin...

Page 17: ...Operating Instructions PMIcontrol Basic M model series FSDM5 46 Mounting L BAL E300 GB 1905 Index 001 Part No 17 48...

Page 18: ...quency inverter with 4 x countersunk screws M5 x 20 3 Fasten the motor connection adapter and make the electrical connection A Fasten the motor connection adapter with 2 x M4 serrated locking nuts 2 5...

Page 19: ...Operating Instructions PMIcontrol Basic M model series FSDM5 46 Mounting L BAL E300 GB 1905 Index 001 Part No 19 48...

Page 20: ...x 20 3 Fasten motor connection adapter and establish the electrical connection For a short cable routing it is alternatively possible to break off the terminal block of the motor connection adapter a...

Page 21: ...Operating Instructions PMIcontrol Basic M model series FSDM5 46 Mounting L BAL E300 GB 1905 Index 001 Part No 21 48...

Page 22: ...ng frequency inverter with 6 x countersunk screws M6 x 20 3 Fasten the motor connection adapter and make the electrical connection A Fasten the motor connection adapter with 4 x M4 serrated locking nu...

Page 23: ...Operating Instructions PMIcontrol Basic M model series FSDM5 46 Mounting L BAL E300 GB 1905 Index 001 Part No 23 48...

Page 24: ...must remain sealed Insert cables properly and ensure tightness of the cable glands Attach the cover of terminal compartment again carefully after connection see Electrical Installa tion Cable inlet l...

Page 25: ...ad to severe personal injury The basic safety and health protection requirements must be ensured in the nal application The device owner is responsible for the EMC of the entire plant according to the...

Page 26: ...pes FSDM5 7 5 8 5 the connection to connectors is made with PUSH IN connection technology Rigid conductors and conductors with wire end ferrules can be plugged directly into the terminal without tools...

Page 27: ...r for motor protection by thermostats TB or thermistors TP factory setting Connection data terminals mains connection FSDM5 7 5 8 5 FSDM12 17 FSDM25 32 39 46 Stripping length 10 mm 8 9 mm 12 13 mm Max...

Page 28: ...exible with wire end ferrule 0 25 mm2 0 25 mm2 Max conductor cross section exible with wire end ferrule 1 5 mm2 1 5 mm2 Min conductor cross section exible with wire end ferrule and collar 0 25mm2 0 25...

Page 29: ...and connection comply with the applicable national and local requirements such as the NEC National Electrical Code or the CEC Canadian Electrical Code Integral solid state short circuit protection doe...

Page 30: ...nection of the device and the protective earth PE is in no case a higher voltage permissible than the indicated line voltage of the device Capacitors are installed between the housing potential and th...

Page 31: ...cooled down i e in case of a connection between the terminals TB TP by switching the line voltage off and back on 5 7 Analog input E1 for setting fan speed The device has an analog input for setting...

Page 32: ...4 V 15 28 V GND E1 E1 1 PWM 10 V E1 D1 GND 10V Analog In 1 10 V DC Out 24V 24 V DC Out PWM f 1 10 kHz 10 k 0 20 mA Control via external setting signal 0 20 mA E1 D1 GND 0 20 mA Analog In 1 E1 1 mA 13...

Page 33: ...V GND A voltage supply is integrated for external devices e g a sensor max current load see technical data In case of overload or short circuit 24 V GND the external power supply is shut down multi fu...

Page 34: ...tor is on GND potential The details of which pull up resistor needs to be used depend on the speci cation on the LED that is used Pull Up 10V OC GND 10 12 2015 i_pmi_basic_status_oc eps 200 300 Displa...

Page 35: ...M MODBUS W AM MODBUS 349045 AM MODBUS W 349050 AM CAN OPEN 349064 CANOPEN module To integrate the device into a CANOPEN network AM LON 349049 LON module To integrate the device into a LON network AM P...

Page 36: ...to too high inside temperatures In case of a temperature rise above the xed limits the modulation is reduced linearly To prevent the complete system being switched off externally in this op eration pe...

Page 37: ...a de ned number of permitted starting tests Permitted starting tests dependant on fault message IGBTand shortcut earth 3 x IGBT Ready 5 x Load driver 8 x Cooling off interval dependant on fault messa...

Page 38: ...ller waits for 5 s cooling phase then the controller attempt a start If a further 250 deactivations occur as a result a nal switch off will occur accom panied by a fault message Should no further swit...

Page 39: ...r of a 4 pole motor For the dimension of the frequency inverter size the rated current of the motor is crucial 4 Max line fuse on site line protection fuse according to EN 60204 1 Classi cation VDE011...

Page 40: ...ctrical Installation Harmonics current for devices 16 A For devices 16 A and 75 A according to EN 61000 3 12 see Electrical Installation Harmonics current and line impedance Max leakage current accord...

Page 41: ...ng line voltage the following table must be observed Maximum motor current at 8 kHz factory setting depending on line voltage and ambient temperature Type 208 V 15 415 V 6 over 415 V 6 480 V 10 40 C 5...

Page 42: ...x 415 480 V 15 5 A 8 kHz 55 FSDM25 3 x 200 415 V 23 0 A 3 x 200 415 V 25 0 A 8 kHz 40 430 x 320 x 214 5 3 x 200 415 V 25 0 A 8 kHz 50 3 x 200 415 V 25 0 A 8 kHz 55 3 x 415 480 V 23 0 A 3 x 415 480 V 2...

Page 43: ...n must comply with the requirements in UL248 and additional to CAN CSA C22 2 No 248 Tests were made with RK fuses without semiconductor protection Maximum sym metrical current Protection rating Maximu...

Page 44: ...ort Circuit Current Rating SCCR The short circuit current rating SCCR is dependent on the device type and article number see also name plate and type key chapter Type Short Circuit Current Rating SCCR...

Page 45: ...stors Thermostatschalter Thermostats UMUN18K0 17 01 2019 q TB TP TB TP W V U M 3 U1 V1 W1 PE TP TP W2 U2 V2 q 3 Motor mit eingebauten Temperaturf hlern with internal thermistors 6 M 3 U1 V1 W1 PE TP T...

Page 46: ...8 4 Dimensions mm FSDM5 7 5 8 5 FSDM12 17 Operating Instructions PMIcontrol Basic M model series FSDM5 46 Enclosure L BAL E300 GB 1905 Index 001 Part No 46 48...

Page 47: ...FSDM25 32 FSDM39 46 Operating Instructions PMIcontrol Basic M model series FSDM5 46 Enclosure L BAL E300 GB 1905 Index 001 Part No 47 48...

Page 48: ...ehl abegg de http www ziehl abegg de 8 6 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for control systems...

Reviews: