Code
Relay
K1
Explanation
Reaction of device
Remedial measures
14
de-energized, 13 -
14 interrupted
Error peak current
If the output current increases above the
speci
fi
ed limit (even in a short time-
frame) the device will switch-o
ff
.
After a switch o
ff
the controller waits for
30 seconds then the controller attempt a
start.
If 10 switch o
ff
s take place consecutively
within 60 s (time to next respective
error),
fi
nal switch o
ff
takes place with an
error message.
Should no further switch o
ff
be exceeded
in 90 sec. the counter will be reset.
15
de-energized, 13 -
14 interrupted
Motor fault
A connected thermostat or thermistor
has tripped the circuit or interruption be-
tween both terminals
“
TB / TP
”
.
Plug for
“
TB
”
or
“
TP
”
in wrong position.
The unit cuts out and does not switch on
again.
Check motor and connection then reset
(
Motor protection).
16
de-energized, 13 -
14 interrupted
Sine
fi
lter to hot
(only in version with integrated sine
fi
lter)
Switch o
ff
at to high temperature, restart-
ing after cooling down.
Check temperature in controller, Check
cooling of the controller.
17
de-energized, 13 -
14 interrupted
Overload fault
The controller was switched o
ff
by the
current limitation.
The error is set after detecting 4 times
(I
2
t-process; maximum overload applied
for 60 s).
After every detection (IGTB Recovery
Flag is set) there is a 30 s wait until a
new attempt is started.
The respective errors must alway have a
shorter interval than 5 minutes (started
after restart). The modulation is switched
o
ff
immediately after every detection.
Check load of the device.
Reset by enable or line voltage ON/OFF.
8
Enclosure
8.1
Technical data
Type
(Part-No.)
Rated current
Output
{1}
[A]
Rated current
(
I
fundamental
component @
50 Hz)
Input
{2}
[A]
Rated temper-
ature
[
°
C]
max. line fuse
{3}
[A]
max. heat dis-
sipation
{2}
[W]
Weight
[kg]
FSDM2.5M
(308251)
2.5
2.5
(2.3)
40
6
50
2.7
FSDM5M
(308238)
5.0
4.8
(4.5)
55
10
90
5.4
FSDM8M
(308239)
8.0
7.1
(6.6)
40
10
140
6.3
FSDM10M
(308262)
10.0
9.4
(8.6)
55
16
200
6.8
FSDM16M
(308302)
16.0
15.2
(14.0)
40
20
360
7.0
FSDM22M
(308314)
22.0
19.2
(17.7)
40
25
520
14.3
FSDM32M
(308316)
32.0
27.6
(25.7)
50
35
700
29.4
Operating Instructions
Fcontrol Basic
–
model series FSDM2.5..50M
Enclosure
L-BAL-E162-GB 2022/02 Index 008
Part.-No.
24/30