5.4 Speed control

Information

We cannot guarantee that competitive brands of voltage control devices and frequency 
converters when used for rotational-speed control of our ventilators will function properly 
and not damage the motor.
The EMC guideline is to be observed in connection with our control units. If the fans are 
completed with components of other manufacturers, the operator is responsible for 
keeping to the EMC guideline 2014/30/EU.

5.4.1 Electronic voltage controllers (phase cutting)

When controlling ventilators using electronic voltage regulators, motor noise can 
occur (due to the system), which can be troublesome.

On fast running ventilators with a high level of air noise, this noise is relatively low. On 
slow running ventilators with a low level of air noise, this noise may be dominant in 
the lower speed range due to the occurrence of resonance.

For systems where noise is critical, we recommend using our 

Fcontrol

 series frequency 

converters with integrated sinusoidal 

lter. 

5.4.2 Frequency inverter

ZIEHL-ABEGG axial fans are suitable for operation with frequency inverters if the 
following points are complied with:

Between the inverter and the motor, sinusoidal 

lters should be incorporated which 

are effective for all phases (sinusoidal output voltage, phase against phase, phase 
against protective conductor) as offered by manufacturers. Please ask for our 
technical information L-TI-0510. 

du/dt 

lters (also called motor or suppression 

lters) cannot be used in place of 

sinusoidal 

lters. 

When using sinusoidal 

lters, screened motor leads, metal terminal boxes and 

a second earth connection to the motor can, if necessary, be omitted. Check-back 
by the supplier of the sinusoidal 

lter. 

If the operational leakage current exceeds 3.5 mA, earthing in compliance with 
DIN EN 50 178, art. 5.2.11.1 must be provided. For this purpose there is a connection 
for a second protective earth on the stator 

ange. Tightening torque 2.7 Nm.

Fcontrol

 = frequency inverter made by ZIEHL-ABEGG

By using the integrated all-pole effective Sine 

lter (phase to phase and phase to 

ground), an absolute parallel control of fans without risk of damage for motors is 
possible. Screened motor cables not required!

Translation of the original operating instructions

Green house fans

Electrical installation

L-BAL-F039-GB 1939 Index 006

Part.-No. 00296810-GB

14/24

Summary of Contents for FB Series

Page 1: ...Green house fans Translation of the original operating instructions Keep for reference L BAL F039 GB 1939 Index 006 Part No 00296810 GB english...

Page 2: ...1 Area of application Notes on use 8 3 2 Note on the ErP directive 9 3 3 Transport storage 9 3 4 Disposal recycling 10 4 Mounting 10 4 1 General notes 10 4 2 Axial fans designs Q and L 11 4 3 ZAplus...

Page 3: ...8 1 Repairs maintenance 17 8 2 Cleaning 19 9 Enclosure 20 9 1 Technical data 20 9 2 Connection suggestion 3 motors with motor protection unit S DT 21 9 3 EU declaration of conformity 22 9 4 Manufactu...

Page 4: ...the device It must be ensured that all persons that are to work on the device can refer to the operating instructions at any time Keep the operating instructions for continued use They must be passed...

Page 5: ...or solids content in the transfer medium Operation with iced up impellers Conveyance of abrasive or adhesive media Conveyance of liquid media Use of the fan and add on parts e g guard grille as a res...

Page 6: ...separate fault and performance monitoring system with an alarm signal function is necessary in order to prevent personal injuries and material damages during malfunc tions and in case the device fail...

Page 7: ...an motor may switch on and off automatically for functional reasons After power failure or mains disconnection an automatic restart of the fan takes place after voltage return Therefore the fan must b...

Page 8: ...he device are never removed and remain legible 2 9 Employment of external personnel Maintenance and service work are frequently carried out by external employees who often do not recognize the speci c...

Page 9: ...when handling Transport the fan s either in the original packaging or in the case of larger fans on the dedicated transportation xtures Holes drilled in support arms wall ring plates and motor block D...

Page 10: ...iling conditions Take into account easy access for cleaning and maintaining the fan Before installing the fan make sure the safety distances are maintained compliant with EN ISO 13857 or in household...

Page 11: ...2 Property class 8 8 friction coefcient ges 0 12 12 Nm 24 Nm 40 Nm Tightening torque guard grille tting 6 Nm Information Since the concrete bolt or screw varies by customer unit these recommendations...

Page 12: ...nections are to be re tightened and damaged lines or cables must be replaced immediately 5 2 Mains connection Attention The fan is intended for the installation as part of a ventilation system and has...

Page 13: ...ts switch after triggering due to excess temperature and independently close after cooling off The fan can then start up If the mains voltage is permanently above 240 V in fan motors for 1 230 V 10 th...

Page 14: ...with frequency inverters if the following points are complied with Between the inverter and the motor sinusoidal lters should be incorporated which are effective for all phases sinusoidal output volta...

Page 15: ...ater drains holes as far as available open or respectively closed according to the suitable installation position 6 Connection data complies with the speci cations on the rating plate During start up...

Page 16: ...elect capacity according to the rating plate Temperature too low for bearing grease Insert bearing with cold greasing see Fan does not run Fan turns too slowly Line failure Undervoltage Check line vol...

Page 17: ...ts are not corrected the device system is potentially very dangerous The device system must therefore not be operated when it is faulty Wear safety clothing shoes and cut resistant safety gloves when...

Page 18: ...for all other damage e g to the coil Regular inspection if necessary with cleaning is necessary to prevent imbalance due to ingress of dirt When opening cable glands on the fan motor check the condit...

Page 19: ...onding to the installation position must be checked for free passage In case of improper cleaning work no warranty is assumed regarding corrosion formation paint adhesion for unpainted painted fans To...

Page 20: ...0 4000 m amsl 1000 m no limitation 1000 m max permissible input current current indication rating plate minus 5 1000 m 2000 m max permissible line voltage max voltage indication name plate minus 1 29...

Page 21: ...urrent sensor to the max permissible current of the connected cable max line fuse 80 A No cut off if the mains supply is interrupted 3 Controller U PE V W N L1 L2 L3 L3 N L2 L1 PE 3 208 415 V 4 mm KT0...

Page 22: ...tor motor with integrated EC controller These products comply with the following EU directives Machinery Directive 2006 42 EC Annex IIA The following harmonised standards have been used EN 60204 1 200...

Page 23: ...address see above K nzelsau 20 04 2016 location date of issue ZIEHL ABEGG SE Dr W Angelis Technical Director Air Movement Division name function signature Translation of the original operating instruc...

Page 24: ...ehl abegg com 9 5 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for control systems ventilation technology...

Reviews: