Example for the alarm maximum message
1. Display actual-value alternates with an alarm message
S:25
°
C SH:99%
Overtemp.
2. In the menu group overview,
“
Alarm
”
“
Alarm ON
”
appears alternately with the pending alarm message.
Alarm
Overtemp.
3. Keep Esc pressed for some seconds to
|
con
fi
rm
|
. The fault message is switched off via the
“
K1
”
relay.
4. As long as a malfunction exists after con
fi
rmation =
“
Alarm pause
”
, the alarm symbol remains lit. If the error
continues (e.g. due to sensor breakage), a message reappears after the adjustable time period for an
“
Alarm
pause
”
–
factory set to 60 minutes).
S:25
°
C SH:99%
5. In the menu group overview,
“
Alarm pause
”
appears alternately with the con
fi
rmed alarmmessage.
Alarm
Overtemp.
6. Past fault messages can be queried in the alarm list.
Overtemp.
Latest alarm = overtemperature
P
↓
00029:49:07
Controllers period of operation at time of message
9.5
Settings for heating
Heating
Heating
The state of the heating is additionally displayed here for informational purposes:
•
Display in two-position controllers (factory setting mode 1 in the installation menu)
–
OFF = Heating is currently switched off
–
ON = Heating is currently switched on
•
Display during linear heating control (see Installation - Heating-Mode 2)
–
0 - 100 %
0 - 10 V or 10 - 0 V
Heating
P
↓
↑
▼
+
▲
=
|
Esc
|
The
two-point mode, 0 - 10 V (linear)
or
Heating inactive
and the sensor input being used as the
actual value is determined in the
“
Heating
”
“
Installation
”
menu. The possible settings are dependent
on the pre-determined mode.
Operating Instructions
Acontrol
–
model series PTE-6AHQ / PTE-10AHQ
Settings for operation
L-BAL-E044-GB 1911 Index 003
Part.-No.
24/36