Potentiometer
set
Function dependently on selected mode of operation
•
For
Speed controller
1.01
without function.
•
For
control with active sensors
4.01
, (0 - 10 V, 4 - 20 mA).
setting range: 0 - 100 %
measuring range of sensor.
Potentiometer
n-min
Minimal output voltage (basic speed)
Setting range: 0 - 100 % (
“
n-min
”
takes priority if over
“
n-max
”
)
Potentiometer
n-max /
Pband
Maximal output voltage
speed limiter
•
Setting range: 100 % -
“
n-min
”
(100 % output voltage = fully clockwise position 30 %)
Dipswitch
S1
Basic setting for device function
Status LED
V13
Indicate the operating conditions over
fl
ashing code
Jumper
E1
Basic setting for kind of signal at analog input
“
E1 = Analog In 1
”
7 Base setup
7.1 Programming of the desired function (Speed controller / PI-Control-
ler)
•
It is possible to use the device as a
“
Speed controller
”
or as a
“
PI-controller
”
. Selection
of the function must
fi
rst be made by setting the internal jumper
“
E1
”
and dipswitch
“
S1
”
.
•
Factory10setting of internal jumper
“
E1
”
in position for 0 - 10 V input signal.
When using other signals bring the jumper in correct position.
•
Factory setting of dipswitches for operatoin as PI-controller
4.01
: 1 + 4 =
|
ON
|
,
2 + 3 =
|
OFF
|
.
In the following the fundamental dipswitch positions for further modes
of operation are represented. Depending upon desired function further adjustments
are necessary (
function dipswitches).
Attention!
Setting of jumper and switches not under voltage! Observe the safety notices!
Changed functions become active partly only after renewed switching on the mains
voltage!
Operating Instructions
Acontrol
PDE-6 / PDE-10
Base setup
L-BAL-E048-GB 1921 Index 005
Part.-No.
16/29