Page 1: ...trol PDE 6 PDE 10 Controller unit PI controller and speed controller for variable voltage 1 fans Operating Instructions Software version D1475A from Version 01 L BAL E048 GB 1921 Index 005 Part No eng...
Page 2: ...2 9 Employment of external personnel 9 3 Product overview 9 3 1 Operational area 9 3 2 Maintenance 9 3 3 Transport 9 3 4 Storage 9 3 5 Disposal recycling 9 4 Mounting 10 4 1 General notes 10 4 2 Minim...
Page 3: ...inimum speed cut off DIP 2 18 7 5 1 For mode Speed controller 1 01 18 7 5 2 For operation as P Controller 4 01 19 8 Start up 19 8 1 Prerequisites for commissioning 19 9 Setting for operation 20 9 1 Sp...
Page 4: ...ing elevated ambient temperatures 25 11 2 Connection diagram 26 11 3 Dimensions mm 28 11 4 Manufacturer reference 29 11 5 Service information 29 Operating Instructions Acontrol PDE 6 PDE 10 L BAL E048...
Page 5: ...ting instructions at any time Keep the operating instructions for continued use They must be passed on to all successive owners users and nal customers 1 2 Target group The operating instructions addr...
Page 6: ...arising from non intended use 2 2 Explanations of symbols Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows Attention General haz...
Page 7: ...ulations Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person This also applies to personnel undergoing general...
Page 8: ...e made on the device All planned modi cations must be authorized by the manufacturer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG These parts were...
Page 9: ...The controller described is used for continuous speed adjustment on variable voltage 1 motors used to drive ventilators or pumps 3 2 Maintenance The device must be checked for soiling and if necessary...
Page 10: ...alled in a location where it will not be disturbed but at the same time can be easily accessed Depending on the housing model use supplied stoppers for cable inlets cut off necessary cable inlets resp...
Page 11: ...d in electricity under the supervision of an electrician in accordance with electrical engineering regulations The 5 electrical safety rules must be observed It is forbidden to carry out work on elect...
Page 12: ...r than 20 m When using a shielded cable connect the shielding to one side only i e only to the control unit with the protective ground keep cable short and with as little inductance as possible 5 2 3...
Page 13: ...ise may be dominant in the lower speed range due to the occurrence of resonance For systems where noise is critical we recommend using our Fcontrol series frequency converters with integrated sinusoid...
Page 14: ...ort circuit 24 V GND the external power supply is shut down multi fuse The device performs a Reset and continues operation It is not permissible to connect voltage outputs of several devices to each o...
Page 15: ...at the connections for the control voltage cannot exceed 30 V between the GND and PE conductor terminals A connection to the PE conductor potential can be made if required t a bridge between the GND t...
Page 16: ...ction Speed controller PI Control ler It is possible to use the device as a Speed controller or as a PI controller Selection of the function must rst be made by setting the internal jumper E1 and dips...
Page 17: ...mA E1 7 2 Select operation mode Simple installation is possible through the use of modes of operation Mode Signal or Sensor input Function 1 01 Signal 0 10 V Speed controller Two step operation 4 01 S...
Page 18: ...compared with the nominal value that has been set The output voltage and hence the rotational speed of the connected motor automatically change as a function of the parameter settings The desired func...
Page 19: ...s place I e always a minimum ventilation is ensured fan does not go under setting n min With minimum air switch off DIP 2 ON For PI controller only in special applications of importance When the setpo...
Page 20: ...er set without function 0 100 n min R 4 8 28 08 2008 v_nmin_pke VSD n min Setting of output voltage at the device 0 100 For setting via external signal Minimum output voltage basic speed Setting range...
Page 21: ...wo variable output voltages two steps Switchover between two steps via external potential free contact possible Step 1 low speed When there is no input signal connected to the input terminal E1 then t...
Page 22: ...er n max 28 08 2008 v_nmax_pband_pke VSD n max P band R 4 9 5 30 n max Pband Maximal output voltage speed limiter Setting range 100 n min 9 2 2 Example Pressure control for ventilation systems Pressur...
Page 23: ...ult Operation as controller 1 01 only for selection 2 10 V or 4 20 mA signal For interruption or short circuit at E1 With reaching minimum or maximum signal values after approx 1 minute de pending on...
Page 24: ...k of 10 fuses 349026 25 W 0 8 1 At rated 230 V values for different speci cations on request 2 Max supply side line fuse according to DIN EN 60204 1 classi cation VDE0113 chapter 1 3 Semiconductor fus...
Page 25: ...t Housing protection IP54 11 1 1 Performance reduction during elevated ambient temperatures The maximum permissible temperature for the rated current at rated voltage is speci ed as rated temperature...
Page 26: ...mA 4 1 E1 V mA GND 24 V M 1 PE U1 U2 1 Motor ohne Thermostatschalter without thermostats 2 1 Line 1 230 V 50 60 Hz 2 1 motor without thermostats 3 Output 10 V Imax 10 mA 4 Input 0 10 V 2 10 V 0 20 mA...
Page 27: ...lerad spanning 1 60 250 V 50 60 Hz N L1 PE max 25 A 1 5 2 4 6 S ET10E I ZB M 1 U1 U2 PE TB q TB Option ZB ZK 2S Kontaktbelastung der Hilfskontakte Contact rating of auxiliary contacts Pouvoir de coupu...
Page 28: ...11 3 Dimensions mm PDE 6 PDE 10 Operating Instructions Acontrol PDE 6 PDE 10 Enclosure L BAL E048 GB 1921 Index 005 Part No 28 29...
Page 29: ...4 info ziehl abegg de http www ziehl abegg de 11 5 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical support for contro...