Trouble Shooting

Malfunction

Cause

Remedical Action

Machine operates, but no ice production

Drive motor and 

Loss of refrigerant

refrigeration unit work

(ventilator runs) 

Refrigeration unit stopped

* No water in water chamber

See water pressure or water level switch 

or works at intervals

above

(drive motor runs)

* Motor cut-out defective

Check / replace

* Compressor defective

Check / replace

Decreased ice production

*

Condenser soiled or insufficient 

Clean with brush or compressed air, 

Poor ice quality

cooling-water flow

never with a wire brush. Water-cooled 
machines: bottle brush, antilime agent

* Ambient temperature too high

Provide better ventilation, 
move maschine away from wall.

* Insufficient amount of refrigerant, 

Remove leak, evacuate circuit, 

bubbles in sight glass

replace filter drier, refill with 
indicated quantity of refrigerant.

* Lime deposit on auger 

Clean freezing unit with hot water and 

or cylinder

antilime agent (Ziegra cleaning agent), 
clean mechanically, if required.

* Ice breaker is misadjusted

see istallation sheet freezing unit

-ZBE 30-110

* Machine runs in intervals

see above (refrigeration unit stopped)  

If Ice maker is connected

* no sufficient refrigerant

check the cooling system of the

to a central refrigeration unit:

* Suction pressure too low

central refrigeration unit

Machine runs in intervals

* pressure fluctuation

Data must comply to the ZIEGRA prescription
(If not at hand, ask Ziegra)

Rumbling or loud squeaking

*

Air bubble in pipe between water

Remove air bubble

noise

chamber and freezing unit

Strong vibrations 
Machine freezes up

*

Lime deposit on auger or

Clean freezing unit with hot water and

cylinder

antilime agent, clean mechanically, 
if required. 

Occasional gentle squeaking noises
are a typical sign for good and hard ice, 
but do not indicate a failure.

Cracking noise in the 

Cylinder bearing defective

Replace

freezing unit

Ice comes out of machine

Even small edges or bends can be 

in pressed form

the cause (see page 2)

("sausages")

6

Repairs of electrical parts and refrigeration circuit only carried out by a 
qualified technician!

Check refrigeration circuit (bubbles 
in sight glass). Eliminate leakage, 
replace filter drier, evacuate circuit, 
refill refrigerant.

After leaving the cylinder the ice is 
pressed due to wrong installation of the 
ice discharge tube, the extension, or 
due to sharp bends.

Summary of Contents for ZBE 30

Page 1: ...uality Miscellaneous 6 Freezing unit 7 Refrigerant and water cicuits 8 wiring diagram attached General installation advice Assembly Instruction Freezing unit Spare parts list Subject to technical modi...

Page 2: ...ng auger does not form part of the refrigeration circuit Therefore leakages in the refrigeration system caused by rotating parts cannot occur The ideal ice temperature is 0 5 C Ziegra chip ice has the...

Page 3: ...e firm installation to main is outside 7 2 9 5 pH consult Ziegra power supply Provide main switch 3 phase machines have a supplied with m c 2 m high pressure hose an phase sequence relay 3 4 sleeve fo...

Page 4: ...n case of too low water pressure or water shortage Automatic restart when the water supply has been restored 4 Compressor Automatic motor cut out in compressor connecting box 5 High pressure switch Th...

Page 5: ...ZBE 110 lift grid and take it off All parts getting in contact with ice ZBE 150 ZBE 375 remove lid ice hose into storage and front panel ice discharge interior or exterior Ice storage melt water grid...

Page 6: ...ambient temperature too high Machine must not be placed in the sun or too warm ambience Improve ventilation condensor soiled Clean with brush or compressed air ventilator motor defective Check replace...

Page 7: ...uns in intervals see above refrigeration unit stopped If Ice maker is connected no sufficient refrigerant check the cooling system of the to a central refrigeration unit Suction pressure too low centr...

Page 8: ...er and the freezing unit into a container o Connect a hose of appr 80 cm with funnel at the water inlet of the freezing unit o Mix cleaning agent with hot water 1 3 bottle agent in 3 4 litre water of...

Page 9: ...Refrigerant and Water Circuit 8...

Page 10: ...01759 301142 Fax 01759 301143 sales wolflabs co uk Use the above details to contact us if this literature doesn t answer all your questions Pricing on any accessories shown can be found by keying the...

Reviews: