Enter Password, first digit entered, prompt for second
digit.
(* Denotes that decimal point will be flashing).

Use the “

Down” key to scroll the value of the second

digit from 0 through to 9, the value will wrap from9
round to 0.

Press the “

Up” key to advance to Up digit.

SysV

SysA

Hz

x1000

kWh

x1000

x1000

2. Measurement Reading Screens

In normal operation the user is presented with one of the measurement reading
screens out of several screens. These screens may be scrolled through one ata
time in incremental order by pressing the “

Up key” and in decremental order

by pressing “

Down key”.

3. Programming

The following sections comprise step by step procedures for configuring the

Ziegler

mfm

3420

for individual user requirements.

To access the set-up screens press and hold the“
Key simultaneously for 5 seconds. This will take the User into the Password
Protection Entry Stage (Section 3.1).

3.1. Password Protection

Password protection can be enabled to prevent unauthorised access to set-up
screens, by default password protection is not enabled.

Password protection is enabled by selecting a four digit number other than 0000,
setting a password of 0000 disables the password protection.

Down” and “

Up”

Enter Password, prompt for first digit.
(* Denotes that decimal point will be flashing).

Press the “

Down” key to scroll the value of the first digit

from 0 through to 9, the value will wrap from 9 round to 0.

Press the “

Up” key to advance to Up digit.

In the special case where the Password is “0000” pressing
the “

Up” key when prompted for the first digit will

advance to the “Password Confirmed” screen.

Screen 2 : Import Energy

Screen 1 : System screen
(System Voltage, System Current,
Frequency)

SysV

SysA

Hz

x1000

kWh

x1000

x1000

Screen 3 : Export Energy

Screen 4 : Max. System voltage andcurrent

SysV

SysA

Hz

x1000

kWh

x1000

x1000

SysV

SysA

Hz

x1000

kWh

x1000

x1000

Screen 5 : Min Sys Voltage & Current

SysV

SysA

Hz

x1000

kWh

x1000

x1000

SysV

SysA

Hz

x1000

kWh

x1000

x1000

SysV

SysA

Hz

x1000

kWh

x1000

x1000

1. Introduction

The

is a panel mounted 96 x 96mm DIN Quadratic Digital

Ziegler

mfm

3420

metering system for the measurement & display of basic electrical parameters like
AC Voltage, AC Current, Frequency, Import energy and Export energy.
The instrument integrates accurate measurement technology (All
Voltage & Current measurements are True RMS upto 15th Harmonic) with 3 line4
digits Ultra high brightness LED display.

Ziegler

mfm

3420

can be configured and

programmed at site for the following : PT
Primary, CT Primary, CT Secondary (5A or
1A)

The front panel has two push buttons through
which the user may scroll through the
available measurement readings, reset the
energy (Import/Export) Min/Max (System Voltage
and System Current) and configure the product.

SysV

SysA

Hz

x1000

kWh

x1000

x1000

Measure d Parameters

System Voltage
System Current
Frequency

Import Energy (8 Digit resolution)

Export Energy (8 Digit resolution)

Uni ts of measu rement

Volts

Amps

Hz

kWh

TABLE 1

kWh

Ziegler

-

mfm 3420

Single Phase

Single Phase Digital Volts, Amps, Frequency & Energy Indicator

Installation & Operating Instructions

Section

Contents

1.

Introduction

2.

Measurement Reading Screens

3.

Programming

3.1 Password Protection
3.2 Set Up Screens

5.

7.

Specification

Installation

5.1

EMC Installation Requirements

5.2

Case Dimensions and Panel Cut-out

5.3

Wiring

5.4

Auxiliary Supply

5.5

Fusing

5.6

Earth / Ground Connections

6.

Connection Diagrams

Down

Up

3.2.1 Potential Transformer Primary value

3.2.2 Current Transformer Primary value

3.2.3 Current Transformer Secondary value

3.2.4 Pulse Rate

3.2.5 Reset
3.2.6 Pulse Duration
3.2.7 Auto Scrolling
3.2.8 Display update Rate
3.2.9 Low Current noise cutoff
3.2.10 Assignment of Pulsed output to

Import or Export Energy

4.

Pulse output option

8.

Connection for Optional Pulse output

Ziegler

mfm 3420

Ziegler

mfm 3420

Digital Multifunction Instrument

www.ziegler-instruments.com

1

|

7

30986_Rev B 05/2007-E1R0

Summary of Contents for mfm 3420

Page 1: ...Sys Voltage Current SysV SysA Hz x1000 kWh x1000 x1000 SysV SysA Hz x1000 kWh x1000 x1000 SysV SysA Hz x1000 kWh x1000 x1000 1 Introduction The is a panel mounted 96 x 96mm DIN Quadratic Digital Ziegl...

Page 2: ...sing the Up key advances the operation to the Up digit and sets the third digit in this case to 5 New Change Password first digit entered prompting for second digit Decimal point indicates that this w...

Page 3: ...imary Value Confirmation stage The minimum value allowed is 1 the value will be forced to 1 if the display contains zero when the Up key is pressed Current Transformer Primary Value Confirmation This...

Page 4: ...and will advance to Auto scroll menu see section 3 2 7 pressing the Down key will re enter the Pulse Duration Edit mode 3 2 7 Auto Scrolling This screen allows user to enable screen scrolling Pressin...

Page 5: ...3 To protect the product against permanent damage surge transients must be limited to 2kV pk It is good EMC practice to suppress differential surges to 2kV at the source The unit has been designed to...

Page 6: ...es at 10s intervals 0 2VA approx Nominal inputcurrent 1A 5A AC rms programmable at site Max continuous inputcurrent 120 of Rated Value Nominal input current burden 0 6VAappro x Max short duration curr...

Page 7: ...torage temperature Relative humidity Warm up time Shock Vibration Enclosure front only Enclosure 96mmx 96mm DIN Quadratic Polycarbonate Housing Screw type terminals 80 mm 0 620 kg Approx Style Materia...