Measurement
specifications
Ranges
resolution
accuracy
Nominal
test
current
10/30/100/500mA/1A
(
-2%
+10%)+6Digits
Current
selection
0.5 x, 1x, 2x, 5 x
nominal current
Trip time
10-2000 ms at 0.5 x
10-500 ms at 1x
10-150 ms at 2x
10-40 ms at 5x
1ms
±(
2%rdg
.+2Digits)
Ramp test
0.4 x to 1.4 times
nominal rated current
10 %
Mains voltage
230
(
+
10%/
-10%
)
V
1v
±(
2%rdg
.+2Digits)
-
Cat III 600V
-
Double insulation
-
IEC 61010-1
-
IEC 61557-6 NF EN 61557-6
-
IEC 61236 (EMC)
-
Locking and warning signals for 400V network voltage
and contact potentail >50V
-
Operating temperature: -15°C /+45°C
-
Storage temperature: -25°C /+70°C
-
IP40