-81-
E-9 DISPLAY
Displayed at the finish of
Forced burning timing.
Explanation 1
In the timing (150 seconds) of the forced burning, the Heater compulsorily gives High burning after the finish of the
forced Med.-High burning until an electric current of the Secondary Flame Rod of higher than 0.3 µA is detected for
longer than 2 sec.
Explanation 2
See Explantion 7 of E-6 Display.
Explanation 3
See Explanation 1 of E-8 Display.
Explanation 4
Make sure that the Secondary Flame Rod is in proper position and free of touching the outer tube on the
earthing side.
Bar Display Illumination
Explanation 1
If the Incomplete Combustion Preventive Device is used in an enclosed room for a long time of period, the
oxygen in the room will be short of oxygen in a level of O
2
vol. % = approx. 18%, to stop the operation.
This Heater reads the temperature (by resistance) of the Burner Thermistor at twenty minutes after the starting
operation and determines operation setting level, at the same time.
The temperature (by resistance), room
temperature change, and the coefficient for combustion condition are calculated and monitored by micro-
computer.
Explanation 2
Check to see if there is any loose screw for the Burner Thermistor. Apply the end of the Burner Thermistor with
an adhesive and securely fasten the Thermistor.
Since the lead wire is thin and, therefore, easily breakable, sufficient care is to be taken not to twist it.
The reference resistances of the Burner Thermistor are shown in the following table.
Since this thermistor is different by a model, use that which suits the model.
Temperature
Color of Lead Wire
250 °C
300 °C
Orange
58 k
Ω
25 k
Ω
Blue
70 k
Ω
31.5 k
Ω
White or Yellow
8 k
Ω
3.34 k
Ω
E-9 is displayed and
the
Heater
is
extinguished.
Excessive Air Safety
Device.
Explanation 1
Insufficient Pump flow rate.
Explanation 2
Earth installing failure
and
nonconforming
wiring.
Fuel Pump filter plugged.
Nonconforming installation
dimensions
of
the
Secondary
Flame
Rod.
Explanation 4
Fuel
Nozzle
plugged.
Correction.
Cleaning
and
part
replacement.
Blower
Motor shows
an
abnormally high revolution.
Explanation 3
Main
Circuit
Board
malfunction.
Fuel
Pump
malfunction.
Main
Circuit
Board
malfunction.
Part replacement.
Bar
display
(--
--)
flickers and the heater
is extinguished.
VENT lamp flickers at
the same time.
Incomplete
Burning
Protector
is
actuated.
Explanation 1
Reignite after giving
sufficient ventilation.
Burner is suddenly cooled
with cool air.
Burner Thermistor failure.
Use
at
a
place
which
is
subjected to direct air, such as
the entrance of the room is to
be avoided.
Correction
or
part
replacement.
10 min. fueling timing is
finished.
FUEL lamp flickers at the
same time.
Burner Thermistor installed
improperly. Explanation 2
The
room
becomes
enclosed and the Heater
starts operation.
Ignition after refuelled
No fuel flow because
water is pooled in the
Fuel
Acceptance
Fitting .
Reignition after draining.