4.18) zero/ span value settings . 

This  operation  will  cause  the  collect  data  is  not  accurate,  please  strictly  according  to  the  following 

instructions:   

Make sure the transducer connection is correct, and the current for no pressure status ;   

In working state, press the "SET" once ,

” PV” shows “ SV ” , then loosen the button . 

Press 

“  SET  “  again  for  5  seconds  ,  it  will  enter  into  output  amplitude  high  limited  value  setting  ,  “  PV 

“ shows “ OL-U “, then loosen the button . 
Then Press 

“ SET “ four times , enter into zero/span value settings , “ PV “ shows “ ESCL “. 

Press    "<" to calibration zero , controller enter into signal load status , 

“ PV” shows “ LOAD ” .   

Load the signal , 

“ SV “ shows value will be changed    ( you through add pressure to load the signal) 

After load signal finished , press    "<" enter into full value conversion settings , 

“ PV “ shows “CNFN “. 

Press "<" to adjust "SV" Numbers flashing, flashing a is modified; 

press    "

" or "

" adjust the flashing value up to down ; 

Setup  completed,  press  "MODE"  button  to  return  to  work,  or  press  the  "SET"  button  enter  into  the  first 

pressure alarm function settings . 

 

4.19 ) the first pressure alarm function settings (SEL1) 

In working state, press the "SET" once ,

” PV” shows “ SV ” , then loosen the button . 

Press 

“  SET  “  again  for  5  seconds  ,  it  will  enter  into  output  amplitude  high  limited  value  setting  ,  “  PV 

“ shows “ OL-U “, then loosen the button . 
Then Press 

“ SET “ five times , enter into the first pressure alarm function settings ,” PV “ shows    “ SEL1” . 

Pressure    "

" or "

" to shift the first pressure alarm function (HJ or LJ ) status . 

Setup  completed,  press  "MODE"  button  to  return  to  work,  or  press  the  "SET"  button  enter  into  the  first 

pressure alarm hysteresis zone setting . 

 

4.20 ) the first pressure alarm hysteresis zone setting ( HC-1) . 

In working state, press the "SET" once ,

” PV” shows “ SV ” , then loosen the button . 

Press 

“  SET  “  again  for  5  seconds  ,  it  will  enter  into  output  amplitude  high  limited  value  setting  ,  “  PV 

“ shows “ OL-U “, then loosen the button . 
Then Press 

“ SET “ six times , enter into the first pressure alarm hysteresis zone setting , “ PV “ shows 

“ HC-1 “ . 
Press "<" to adjust "SV" Numbers flashing, flashing a is modified; 

press    "

" or "

" adjust the flashing value up to down ; 

Setup completed, press "MODE" button to return to work, or press the "SET" button enter into the second 

pressure alarm function settings . 

 

For example : 

according to the 3 settings different value , The first pressure alarm (AL-1) value,    the first 

pressure alarm function (SEL1 )    and the first pressure alarm hysteresis zone ( HC-1)   

 

Example 1 :   

if setting the AL-1 as 

“5.00 “ , setting the SEL-1 as “HJ” , setting the HC-1 as “ 0.20 “ .   

In working state, AL-1 relay working status as following    : 

 

Summary of Contents for PD9001

Page 1: ...Shanghai Zhaohui Pressure Apparatus Co Ltd www zhyqsensor com info zhyqsensor com Tel 86 21 51691919 Fax 86 21 67755185 ZHYQ Digital Controller Operation Manual PD9001...

Page 2: ...lity and reliability of the system The instrument technical indicators are as follows Digital Display Double layer double color four digital display green and red Electronic bar display 20 segments el...

Page 3: ...key m SET Function key the pressure value would be zero clearing if you press thefunction key and AC reset key at the same time n Shift key if you mistake the zero clearing operation now you need to...

Page 4: ...hielded shielded 14 220V power supply input L 7 PID output PID output 15 220V power supply input N 8 PID output PID output 16 Ground 2 4 2 transducer input 4 20mA 0 5V 0 10V terminal Function transduc...

Page 5: ...ure range 1 9999 According to the transducer full range 1000 DOT Decimal point location selection 0000 000 1 00 01 0 0001 dddd no decimal ddd d 1 decimal dd dd 2 decimal d ddd 3 decimal 00 01 ESCL Zer...

Page 6: ...ctual output value for example if output type 4 20 mA SV shows a value of 80 0 the actual output value of 16 8 mA Press reduce output Press increase the output 4 3 Sampling data reset make sure connec...

Page 7: ...djust the flashing value up to down After enter the password press SET to validate initial password 0000 Password authentication is passed enter into new password Settings PV shows NPAS Press the adju...

Page 8: ...enter into AL 2 parameter Settings 4 13 The second pressure alarm AL 2 value settings In working state press the SET six times PV shows AL 2 Press to adjust SV Numbers flashing flashing a is modified...

Page 9: ...sducer pressure range value settings Instrument range should be match with the instrument range setting value then it will display the properly pressure value so firstly check the transducer range if...

Page 10: ...the SET once PV shows SV then loosen the button Press SET again for 5 seconds it will enter into output amplitude high limited value setting PV shows OL U then loosen the button Then Press SET five t...

Page 11: ...essure alarm function HJ or LJ status Setup completed press MODE button to return to work or press the SET button enter into the scond pressure alarm hysteresis zone setting 4 22 the second pressure a...

Page 12: ...high limited value setting PV shows OL U then loosen the button Then Press SET eleven times enter into the output adjustment cycle settings PV shows TS press or to adjust SV value Setup completed pres...

Page 13: ...el Range bar Input Output Power Supply Alarm Other requirement PD9001 Example PD9001 350BAR 4 20mA 0 10V 220V 2 7 ZHYQ contacts Company Name Shanghai Zhaohui Pressure Apparatus Co Ltd Address 5 6F No...