DS5210 Series Digital Electrical Meter 

User Manual 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for DS5210 Series

Page 1: ...DS5210 Series Digital Electrical Meter User Manual ...

Page 2: ...e power reactive power power factor and so on It is widely used in electric power monitoring industrial automation switch cabinet and various intelligent distribution system Features High precision can measured normal waveform Digital display can set the ratio of voltage and current Easy for installation and connection Input impedance 2MΩ Input output protection function meter will be Long life an...

Page 3: ...DS5210 系列数显电测量仪表 XXXX XXX XXX 使用说明书 共 8 页 第 2 页 ...

Page 4: ...ive power meter Q Reactive power meter PF Power factor meter F Frequency meter Combination parameter UIP UIF Connection 1 Single phase 2 Three phase three wire 3 Three phase four wire Meter Dimension 10 96mm 96mm 20 96mm 48mm 30 72mm 72mm 40 48mm 48mm 50 80mm 80mm 60 120mm 120mm LED Display Meter Code Company Code ...

Page 5: ... Measurement network 单相 Nominal input AC Voltage AC 100V 220V 380V 500V AC Current AC 1A 5A Linear range Voltage 10 120 Nominal input value Current 1 120 Nominal input value Frequency 45Hz 65Hz Power Factor 0 1 Delay 1 0 0 1 Leading Allowable Overload Continue 1 2 times Instantaneity Voltage 2times 5s Current10times 5s Display HHHH when exceed the rated value Output charac terist ic Accuracy grade...

Page 6: ...Burst Immunity 2 Grade GB T17626 4 Surge immunity 4 Grade GB T17626 5 Security features Insulation strength Input and auxiliary power supply AC2 5kV 1min insulation resistance 100MΩ Heat resistance and flame retardant Terminal 960 Case 650 actuation duration 30s environme nt Temperature Operation 25 55 Storage 25 50 Humidity 93 RH Non Dewfall Non corrosive gas Altitude 2500m Installation method Em...

Page 7: ...90 90 91 91 20 96 48 90 44 92 45 30 72 72 66 66 68 68 40 48 48 44 44 45 45 50 80 80 66 66 68 68 5 1 Installation Embedded installation mode open the hole in the panel according to the Panel open size in the instrument Put the meter to the panel and embedde d into the installation hole and clamp the clamping piece into the instrument corresponding to the clamping groove 5 2 Connection mode ...

Page 8: ... should make sure the connection is correct If the wiring diagram on the specification and the wiring diagram on the instrument case are not consistent Please refer to the wiring diagram on the instrument case 1 Voltage meter signal input 5 2 2 Current meter signal input ...

Page 9: ...DS5210 系列数显电测量仪表 XXXX XXX XXX 使用说明书 共 8 页 第 8 页 5 2 3Power meter combined meter signal input ...

Page 10: ...5 2 4 Frequency meter signal input 5 2 2 Auxiliary power supply 5 3 Connection description 5 3 1Instruments need to be applied to the auxiliary power supply Please make sure that the supplied power is suitable for meter to prevent damage to the meter ...

Page 11: ... be one end of the grounding in order to maintain convenience Voltage input terminal is recommended to use with fuse 5 3 3 Input current should not be higher than the rated current of the products or should consider to use the current transformer current transformer should one end of the grounding in order to maintain convenient 5 4 Panel and operation instructions DS5210 series panel is shown as ...

Page 12: ...值指示 显示窗口 单位倍率 测量值单位 D O S S Y R 左上英文为 Display 左下为 Negative indication 右上为 Unit 右下为 Unit rate 最下面依次为 Left shift keys Right shift keys Programming keys Return keys k M 显示窗口 负值指示 单位倍率 测量值单位 左移键 右移键 编程键 返回键 SET D O S S Y R 左上英文为 Display 左下为 Negative indication 右上为 Unit 右下为 Unit rate ...

Page 13: ...will rapid decrease Programming keys SET Used to enter the programming and modify the parameter values to save the parameter values and return to the superior menu Return keys Used to cancel the values when it is in programming mode Can push the keys until measured value display 5 4 3 Programming parameter description Parameter type Parameter code Parameter name Setting range description System Vo...

Page 14: ...input the password use to move and change the number to 816 then push SET to the programming system 2 Then the meter will display so you can change the Voltage ratio if need change other item need push Then the meter will display to and after setting use SET to save the operation 3 If push will return to the last menu If no operation within 60 second the meter will return to the display state Prog...

Page 15: ...ingle phase meter 5 4 4 Abnormal display instructions HHHH The measured value is out of range The voltage or current input exceeds 1 2 times of rated value of the instrument 测量模式 编程口令 SET SET SET SET SET SET 编程模式 测量模式 编程口令 SET SET SET SET SET SET 编程模式 ...

Page 16: ...f the environment should meet the technical requirements 6 Maintenance Instrument should be verification at least one time each year if the meter deviation exceeds the range usually it cause by damp dust or corrosive gases we can dry and clear to recovery the accuracy If it not works need send back to the factory to repair The meter have guarantee for 12 months user should follow the instructions ...

Page 17: ... shall conform to the provisions of 9329 1999 JB T Storage temperature of the environment is 25 degrees Celsius to 50 degrees Celsius the relative humidity of not more than 85 and the harmful substances contained in the air is not enough to cause the corrosion of the instrument ...