Quick operation manual

 

Page

 2/7 

AC 3×220/380V

AC 3×230/400V 

AC 

5(80)A 

400imp/kWh(imp/kvarh) 

Pulse signal 

output 

Supply active

reactive energy optical signal and 

optocoupler collector open-circuit electrical signal impulse 

output, pulse length:80±16ms

 

Auxiliary 

function 

Protocol   

Support MODBUS-RTU communication Consultation, 

Baud rate support 2400bps, 4800bps, 9600bp. 

Note 1

the other performance index, indoor table reference IEC 62053 - 21 requirements.   

2.

 

Wiring instructions:   

       

 

  Figure 1 DTSU666-

□series                                               

     Figure 2 DSSU666-

□series

 

       

 

Figure 3 DTSU666-

□series                                                   

    Figure 4 DSSU666-

□series

 

Current signal wire 

1-------L1*(phase L1 current input line)      3------L1(phase L1 current output line)   
4-------L2*(phase L2 current input line)      6------L2(phase L2 current output line )   
7-------L3*(phase L3 current input line)      9------L3(phase L3 current output line ) 

Voltage signal wire 

2-------L1(phase L1 voltage line)             5-------L2(phase L2 voltage line)   
8-------L3(phase L3 voltage line)            11-------UN(Neutral line) 

RS485 communication line 

15-------A

RS485-A

 

 

 

 

             16-------B

RS485-B

 

Energy pulse output line     

20-------active ,reactive energy pulse +              21------- Energy pulse – 

3.

 

Instructions of programming parameters 

Instruction of keys: “

” means “confirm”

  “

  ”means “exit”, “

  ”means “add”. Input 

the password(assumed to be 701),enter the submenu item of “system settings”(when the system is set 
to third rows of digital display, the first row of hidden): 

 

Summary of Contents for DTSU666 Series

Page 1: ...The terminals are not connected according to the requirements 1 Technical parameters Table 1 Technical parameters Index Input signal Measuring network 3 phase 3 wire DSSU666 series 3 phase 4 wire DTS...

Page 2: ...series Current signal wire 1 L1 phase L1 current i nput l ine 3 L1 phase L1 current output line 4 L2 phase L2 current i nput l ine 6 L2 phase L2 current output line 7 L3 phase L3 current i nput l ine...

Page 3: ...5 the settings of the common parameters 4 Installation size Table2 Model Shell size width length depth DIN rail for mounting DTSU666 series DSSU666 series 126mmx89mmx76mm 35mm Figure 6 outside view 5...

Page 4: ...ion parameter value 0 1 0000H REV version signed int 1 R W 0001H UCode Programming password codE signed int 1 R W 0002H ClrE Electric energy zero clearing CLr E 1 zero clearing signed int 1 R W 0003H...

Page 5: ...power the unit is var Floating Inverse AB CD 2 R 201CH Qa A phase reactive power the unit is var Floating Inverse AB CD 2 R 201EH Qb B phase reactive power the unit is var invalid when three phase thr...

Page 6: ...CD 2 R 4046H Q3Eq current quadrant reactive total energy Floating Inverse AB CD 2 R 4048H RESERVED reserved Floating Inverse AB CD 2 R 404AH RESERVED reserved Floating Inverse AB CD 2 R 404CH RESERVED...

Page 7: ...cturer Zhejiang CHINT Instrument Meter Co Ltd Address Bridge Industrial Zone 325603 Wenzhou Zhejiang China P C 325603 Technical Support Hotline 0571 56977777 7659 86 15858113737 Quality Complaints 057...

Reviews: