background image

Packed Receiver 

 

for Energy Harvesting Switch (AFZE) 
OPERATING MANUAL

 

V03 EN Aug 2017 (BA_Empfaenger_EN_V03) 

ZF Friedrichshafen AG 

   

 

1

 

 

 
1 Safety guidelines 

 

WARNING: Danger to life 

• Do not install this product as part of a 
   safety-relevant, life or health preserving 

                   facility.  
  

 

CAUTION: Damage to the device due to 
electrical discharge 

• Observe the ESD protection. 

 

CAUTION: Damage due to liquid in the 
device 

• Prevent liquid from getting inside the 

                    components.  
• Do not use solvents such as benzine or alcohol, or 
   scouring agent and scourers for cleaning.  
 

2 Area of application 

The receiver module was designed to receive radio 
frequency signals from energy harvesting switches 
(AFIM / AFIS). The receiver is suitable for wall or rail 
installation in the area of automation technology and 
has different connection options.   

3 Interfaces

 

  

3.1 Power supply interface to connect the 
      power using the external supply 

 
Use the „Power supply“ interface to connect the 
power using an external supply. The external supply 
must be galvanically isolated. The input voltage may 
total 7 to 24 V DC.   

1

 

Observe the polarity (left + right – when viewed 
from the front) 

2

 

Connect the external supply using the spring 
terminal (wire diameter 0.5 to 1.5 mm2). To do 
so, press the spring downwards by inserting a 
screwdriver into the smaller opening, and by 
pushing the wire into the larger opening.  

 

 
 
 
3.2 USB service interface  

The USB interface is used for communicating with a 
PC and for connecting power using a USB Micro-B 
plug. The interface can be used for evaluating data 
received wirelessly for service purposes. The interface 
is protected from short circuits by a 500 mA SMD 
fuse. Observe the maximum values for the USB 
interface standard.  
If the receiver is already connected to the power 
supply interface when the USB is connected, then a 
reset must be carried out in order for USB 
communication to function. 

3.2.1 USB transmission parameters 

The USB connection appears as a virtual COM port in 
the PC. You can configure it on the PC any way you 
like.  
If a transmitter has not been paired, then information 
from all transmitters will be output (see 3.4.3 „TTL 
data format“). If at least one transmitter has been 
paired, then only the paired transmitters will be 
output.  
 

Name 

Value 

Data rate 

57600 Baud 

Start bit 

Data bit 

Stop bit 

Parity 

None 

3.3 Relay connection  

Spring terminals are used for connection (wire 
diameter 0.5 to 1.5 mm2). 

 

To do so, press the spring downwards by inserting

 

   a screwdriver into the smaller opening, and by 
   pushing the wire into the larger opening. 

 

3.3.1 Relay positions 

 

 

 
 
 

 
 
 
 
 
 
 

 
 
 
 
3.3.2 Relay contact service life  

Connection values:  
6 A, 250 VAC resistive load 
6 A, 30 VDC resistive load  

 

 

     

 

3.4 TTL interface

 

 

CAUTION: Excess PC voltage will 
damage the device. 

 

• Use a higher-level control unit for data 
   communication.  
• Do not connect the receiver directly to a PC using 
   the RS 232 interface. (The voltage level of the RS 
   232 interface on the PC totals 12 V, the TTL voltage 
   level totals 5 V). 

 

When receiving data from a paired transmitter, the 
following information is output via the interface:  

 

Unique ID of the transmitter  

 

Switch information (pressed or released)  

 

Number of telegrams received  

 

Signal reception strength in dBm (see 3.4.3 „TTL 

   data format“)  
 
 
 
 
 
 
 
 
 