Installation and operating instructions V00 67
10.2 AC output data
Type
Zeverlution Pro 33K
Power connection
Three phase
Rated output power
30000W
Max. output active power
(1)
33000W
Max. output apparent power
(2)
33000VA
Rated grid voltage
3/N/PE, 220/380V
3/N/PE, 230/400V
3/N/PE, 240/415V
AC voltage range
(3)
160 V to 300 V
Operating range at AC mains
frequency 50 Hz
(4)
45 Hz to 55 Hz
Operating range at AC mains
frequency 60 Hz
(4)
55 Hz to 65 Hz
Max. output current
3×48A
Power
factor
VDE-AR-N 4105
0.85ind - 0.85cap
Other safety regulations
>0.97 at 20% load, >0.99 at 100% load
Recommended AC circuit breaker
300V,63A,
TYPE C circuit breaker
Total current harmonic wave
distortion factor (THD)
<3% (rated power)
Evening loss
< 1 W
Standby loss
< 12 W
(1) Max. output active power is 30000W for Australia market.
(2) Max. output apparent power is 30000VA for Australia market.
(3)The AC voltage range should comply with the local safety standards.
(4)The AC frequency range should comply with the local safety standards.