Zetkama 221 User Manual Download Page 4

4/12 

 

 
 
 
 

 
             

the use of additional leverage when turning the wheel is prohibited 

            the closing cannot exceed the value of "0 -0" on the wheel 

 

 

operation of installed valves can be checked by repeated opening and closing 

                                                                                             

 

To ensure the safe operation of each valve, especially of the ones that are rarely used, they should be    

  regularly monitored. Inspection frequency should be determined by the user. 

 

 
 

8. MAINTENANCE AND REPAIR 
 

The balancing valves fig. 221 do not require any maintenance provided that they are used in accordance with 

their intended use. 

 
 

 

Before taking up any maintenance actions, make sure the flow of medium in the pipeline was cut off, the    

  pressure was reduced to ambient pressure, medium was removed and the system was cooled down. 
 

 

all  maintenance  and  repair  work  should  be  performed  by  qualified  personnel  using  suitable  tools  and 
original spare parts. 

 

during maintenance and servicing use personal protective equipment appropriate to the risk involved, 

 

after removing the valve, replace the seals with which the valve is connected to the pipeline system,  

 

each time when the cover is removed, clean the valve sealing surface and apply new gasket of the same type 
as previously used 

 

tightening the cover to the body must be made with the valve opened (disc in the upper position) 

–   before reassembling the valve in the pipeline it is necessary to check valve operation and tightness of all     
     connections. Tightness test should be carried out with water pressure of 1,5 x nominal pressure of the valve. 

        
                                                                                         

9. VALVE SETTING Fig. 221 
 

The valve opening degree can be read on the dial and its lateral part 
Number of turns between the closed and fully open positions is: – 4 
Locking the setting 

 

for the proper adjustment of valve opening tables and flow charts drawn up for each valve size should be used, 

 

  So adjusted balancing valve can be closed many times now, but its opening is only possible to the set value. 

 