SURFACE MOUNTING – The Surface Box can be fixed to the wall using 
standard wall fixings through a choice of the holes provided. Cable entry 
can be made through back wall or through side wall where indicated. Cable 
glands up to 20mm diameter can be fitted in area marked on product 
pointing vertically towards ceiling or floor 

 

FLUSH MOUNTING – The Surface Box can be discarded and the Call 
point mounted onto any UK standard single-gang back box with a 
minimum depth of 16mm. 

All Call Point Models 

Mounting  

Drill up to 20mm for 
Cable Glands 

 Standard Wall Fixings

PAGE 5 

Summary of Contents for ZT-CP2

Page 1: ...RESETABLE CALL POINTS INSTALLATION AND USER MANUAL FULLY COMPLIES WITH EN54 11 ISSUE 1 DATE 15 8 05...

Page 2: ...Model No ZT CP1 Part No 43 301 Type A Call Point PAGE 2...

Page 3: ...Model No ZT CP2 Part No 43 300 Type B Call Point PAGE 3...

Page 4: ...Call Point Dimensions TYPE A TYPE B PAGE 4...

Page 5: ...e wall where indicated Cable glands up to 20mm diameter can be fitted in area marked on product pointing vertically towards ceiling or floor FLUSH MOUNTING The Surface Box can be discarded and the Cal...

Page 6: ...All Call Point Models Wiring the Call Point ve IN OUT ve IN OUT Screw Terminals accept 0 28 2 5mm conductors There is no direct contact to the micro switch PAGE 6...

Page 7: ...All Call Point Models Operation ACTIVATED FLAG SHOWING LED ON 1 2 TYPE A PRESS TYPE B 1 BREAK SNAPLATCH 2 LIFT AND PRESS PAGE 7...

Page 8: ...Point Models Resetting the Call Point Insert Key 1 into Reset Barrel 2 Turn Key Clockwise The Flag 3 retracts and Operating Element 4 springs forward The LED 5 will turn off Unit is now reset 5 4 1 2...

Page 9: ...All Call Point Models Test TEST 1 Insert Key 2 Turn 90 o Clockwise 3 LED will turn on 4 Return to stop PAGE 9...

Page 10: ...only 3 Set Dipswitches and mark label with call point address ALL Call Points 4 Fit mounting screws as shown tighten 5 Lift Flag 6 Return Operating Element 7 Ensure unit operational by pressing operat...

Page 11: ...1 0 0 1 1 1 0 58 0 1 0 1 1 1 0 59 1 1 0 1 1 1 0 60 0 0 1 1 1 1 0 61 1 0 1 1 1 1 0 62 0 1 1 1 1 1 0 63 1 1 1 1 1 1 0 64 0 0 0 0 0 0 1 65 1 0 0 0 0 0 1 66 0 1 0 0 0 0 1 67 1 1 0 0 0 0 1 68 0 0 1 0 0 0...

Page 12: ...ew parts please use these Part Nos Part No CODE Description 43 300 ZT CP2 CONVENTIONAL CALL POINT TYPE B RESETABLE 43 301 ZT CP1 CONVENTIONAL CALL POINT TYPE A RESETABLE 43 302 ZT CP2 F CONV FLUSH CAL...