User Guide of ZT-30P 

10 

Issue 1 / Rev.1 

Techncial Specification 

Model

 

ZT-30P 

 

Part Number

 

47-156

 

Spectrum Response

 

UV/IR (Dual Bands)

 

Spectrum Response

 

(at highest sensitivity setting for 
0.1m

2

 pan fire) 

Fuel 

n-Heptane 
Gasoline 
Diesel 
LPG* 
Ethanol 
IPA 
Methane**

 

Distance 

30m 
30m 
20m 
20m 
20m 
25m 
20m

 

*0.5m high/0.2m width plume fire, **30” plume fire

 

Response Time

 

Typically 5 seconds

 

Adjustable Time Delay

 

Up to 20 seconds

 

Sensitivity Range

 

4 sensitivity ranges for 0.1m

n-Heptane pan fire from 15m to 65m

 

Field of View

 

Horizontal / Vertically Typical  120º & 120º Max

 

Built-in-Test

 

Automatic self-check to verify the lens cleanliness/electronic circuits & etc

 

Temperature Range

 

Operating/Storage:-40ºC to 75ºC

 

Humidity

 

Up to 95% non-condensing

 

Operating Voltage

 

24VDC nominal (18-32VDC)

 

Power Consumption

 

Standby: max. 50mA, Alarm: max. 70mA

 

Cable Entry

 

1 x Ø6mm

 

Wiring

 

According to the requirements

 

Electromagnetic Compatibility

 

Complies with EN 61000-6-4 and EN 50130-4

 

Electrical Interface

 

4-Wiring relay contact outputs

 

Relays

 

Alarm(N.O.), Fault(N.C) 
SPST volt-free contacts rated 5A at 30VDC or 250VAC

 

RS-485 (option)

 

RS-485 Modbus compatible communication link that can be used in computer 
controlled installations

 

Summary of Contents for ZT-30P

Page 1: ...Flame Detector Model ZT 30P User Guide Document Ref GLT 300 7 1 Zeta Alarms Limited 72 78 Morfa Road Swansea SA1 2EN United Kingdom Phone 441792 455 175 Fax 441792 455 176 Website www zetaalarmsystems...

Page 2: ...User Guide of ZT 30P 2 Issue 1 Rev 1...

Page 3: ...d 5 3 Install 6 4 Operation 7 5 Operation Technical Specification 8 LIST OF FIGURES Figure 1 Product Contents Outline Indication 4 Figure 2 Change of DIP Switch Setting 5 Figure 3 Final Installation A...

Page 4: ...User Guide of ZT 30P 4 Issue 1 Rev 1 1 Unpack Checking Contents Unpack the delivered pack and check the following contents Figure 1 Product Contents Outline Indication...

Page 5: ...TOP Cover Base cover and change the Setting of the DIP Switch Figure 2 Change of DIP Switch Setting 2 After completing the change of DIP Switch Setting combine the TOP Cover and BASE Cover by screwin...

Page 6: ...rs through three 3 holes of detector mounting bracket Release the locking three 3 Hexagonal Socket Set Screws in such a way that allows rotating detector and point the detector towards the protected a...

Page 7: ...e start up procedure has finished and no faults are present the detector will begin normal operation Green LED will remain on Table1 Output Signals LED Indicator versus Detector State Detector Status...

Page 8: ...tor delays the execution of the Alarm output relay by the specified period of time The detector will then additionally evaluate the fire condition during the specified Alarm Delay Time If the Alarm le...

Page 9: ...User Guide of ZT 30P 9 Issue 1 Rev 1 Notes 1 denotes an example of optional colour wirings...

Page 10: ...m Field of View Horizontal Vertically Typical 120 120 Max Built in Test Automatic self check to verify the lens cleanliness electronic circuits etc Temperature Range Operating Storage 40 C to 75 C Hum...

Page 11: ...hite powder coating Mounting Tilt Mount Heavy duty copper free aluminium with white powder coating Dimensions Detector 63 D x 110 L mm Weight Detector Mounting Bracket Aluminium 0 3kg Water and Dust I...

Reviews: