Zeta PREMIER EX8 User Manual Download Page 5

Extinguishing Panel - USER MANUAL 

 

Approved Document No: GLT.MAN-132

 

 

PAGE 5

 

Issue : 1.2         Author: NRPJ      Date: 06/10/2010

 

The Premier EX8 has the following LED indicators:- 
 

LED 

COLOUR 

FUNCTION / MEANING 

 

 

 

POWER 

GREEN 

The panel is supplied with power, either battery, mains or both 

COMMON FIRE 

RED 

There is an alarm on the system. Check which zone caused the alarm 

COMMON FAULT 

YELLOW 

There is a fault on the system. Another LED(s) will be lit to indicate the specific fault 

BATTERY FAULT 

YELLOW 

There is a problem with the batteries. Rectify or replace. 

CHARGER FAULT 

YELLOW 

The panel is not charging the batteries (usually mains fail or low mains) 

LOW BATTERY 

YELLOW 

The batteries are below their final voltage & should be replaced 

EARTH FAULT 

YELLOW 

Problem in system wiring. At least one cable is shorting to earth. 

EXT.FAN DISABLE 

YELLOW 

The external equipment relay has been disabled 

SYSTEM FAULT 

YELLOW 

The CPU has crashed, (Or CPU reset has been pressed & held) 

REMOTE FAULT 

YELLOW 

The panel has received a fault input from external equipment 

REPEATER FAULT 

YELLOW 

The panel has lost communication with the repeater panel 

GEN S/C FAULT 

YELLOW 

Indicated that a line fault is caused by a short circuit 

 

 

 

EXTINGUISHANT RELEASED 

RED 

The bottle output has been activated & the gas released 

RELEASE IMMINENT 

RED 

The panel has started the release timer and will activate bottle imminently 

HOLD/ABORT 

YELLOW 

An emergency hold OR emergency abort input has been activated. 

MANUAL RELEASE 

RED 

A manual release call point has been activated 

1

ST

 STAGE ALARM 

RED 

One of the crossed zones is in alarm 

2

ND

 STAGE ALARM 

RED 

Both of the crossed zones are in alarm 

LOW PRESSURE 

YELLOW 

A drop in bottle pressure has been detected 

FLOODING ZONE FAULT 

YELLOW 

There is a fault relating to the flooding zone1 (ie the extinguishing section of the panel) 

MANUAL MODE 

YELLOW 

The panel is in manual only mode (ie will not be triggered by detectors) 

AUTOMATIC MODE 

GREEN 

The panel is in automatic or manual mode  

 

 

 

GENERAL DISABLEMENT 

YELLOW 

Lights when any section of the system is disabled 

GENERAL TEST 

YELLOW 

Lights when any section of the panel is in test mode 

CONTROLS ACTIVE 

YELLOW 

Lights when controls enabled keyswitch is on 

 

 

 

ZONE 1-6 FIRE 

RED 

Lights when one of the detection zones is in alarm 

ZONE 1-6 FAULT 

YELLOW 

Lights when one of the detection zones has a fault 

ZONE 1-6 TEST 

YELLOW 

Lights when one of the detection zones is in test mode 

ZONE 1-6 DISABLED 

YELLOW 

Lights when one of the detection zones is in disablement mode 

 

 

 

1

ST

 STAGE SNDR  ACTIVE 

RED 

Lights when the first stage sounder is on 

1

ST

 STAGE SNDR FAULT 

YELLOW 

Lights when the first stage sounder has a wiring fault 

1

ST

 STAGE SNDR TEST 

YELLOW 

Lights when the first stage sounder is in test mode 

1

ST

 STAGE SNDR DISABLED 

YELLOW 

Lights when the first stage sounder is disabled 

2

ND

  STAGE SNDR ACTIVE 

RED 

Lights when the second stage sounder is on 

2

ND

  STAGE SNDR FAULT 

YELLOW 

Lights when the second stage sounder has a wiring fault 

2

ND

  STAGE SNDR TEST 

YELLOW 

Lights when the second stage sounder is in test mode 

2

ND

  STAGE SNDR DISABLED 

YELLOW 

Lights when the second stage sounder is disabled 

BOTTLE OUTPUT ACTIVE 

RED 

Lights when the bottle output is on 

BOTTLE OUTPUT FAULT 

YELLOW 

Lights when the bottle output has a wiring fault 

BOTTLE OUTPUT DISABLED 

YELLOW 

Lights when the bottle output is disabled 

1

ST

 STAGE RELAY ACTIVE 

RED 

Lights when the first stage relay is on 

1

ST

 STAGE RELAY  TEST 

YELLOW 

Lights when the first stage relay is in test mode 

1

ST

 STAGE RELAY DISABLED 

YELLOW 

Lights when the first stage relay is disabled 

2

ND

  STAGE RELAY  ACTIVE 

RED 

Lights when the second stage relay is on 

2

ND

  STAGE RELAY  TEST 

YELLOW 

Lights when the second stage relay is in test mode 

2

ND

  STAGE RELAY  DISABLED 

YELLOW 

Lights when the second stage relay is disabled 

 

 

 

MAN.L RELEASE INPUT ACTIVE 

RED 

A manual release call point connected to the remote input has been activated 

MAN. RELEASE INPUT FAULT 

YELLOW 

Fault in wiring to Manual release call point 

MAN. RELEASE INPUT  DISABLED 

YELLOW 

Manual release call point circuit is disabled 

GAS FIRED INPUT ACTIVE 

RED 

The panel has received a signal from the cylinder to say the gas has been released. 

GAS FIRED INPUT FAULT 

YELLOW 

There is a wiring fault to the bottle`s sensor 

EMERG. HOLD INPUT ACTIVE 

YELLOW 

The emergency hold input has been activated 

EMERG. HOLD INPUT FAULT 

YELLOW 

Fault in wiring to Emergency hold switch 

EMERG. ABORT INPUT ACTIVE 

YELLOW 

The emergency abort input has been activated 

EMERG. ABORT INPUT FAULT 

YELLOW 

Fault in wiring to Emergency abort switch 

AUTO/MANUAL INPUT ACTIVE 

YELLOW 

The panel has been set to manual mode by a remote input 

AUTO/MANUAL INPUT FAULT 

YELLOW 

Fault in wiring to Auto / Manual switch 

PRESS. SWITCH INPUT ACTIVE 

YELLOW 

The bottle`s pressure switch output has been activated 

PRESS. SWITCH INPUT FAULT 

YELLOW 

Fault in wiring to bottle`s pressure switch 

BOTTLE SCALES INPUT ACTIVE 

YELLOW  

The bottle`s scales switch has been activated 

BOTTLE SCALES INPUT FAULT 

YELLOW 

Fault in wiring to bottle`s scales switch 

 

 

 

ACCESS LEVEL 3 

YELLOW 

Access level 3 selected 

GAS RELEASE COUNTER 

YELLOW 

Gas release counter is being displayed on 3 digit display 

RELEASE DURATION TIME 

YELLOW 

Release duration time is being displayed on 3 digit display

 

RESET INHIBIT TIME 

YELLOW 

Reset inhibit time is being displayed on 3 digit display

 

 

 

 

Summary of Contents for PREMIER EX8

Page 1: ...EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 EN54 PARTS 2 4 USER MANUAL Approved Document No GLT MAN 132 Issue 1 2 Author NRPJ Date 06...

Page 2: ...PANEL OPERATION 7 Normal Operation 7 Fire Alarm Condition Peripheral Zones 7 What to do in the event of a fire 7 Resetting from an alarm condition 7 First Stage Alarm 8 Second Stage Alarm 8 Hold Abor...

Page 3: ...fired The panel has remote inputs for Start Stop Sounders Silence Reset to allow the panel to be controlled remotely The panel has Open collector repeat outputs for most panel status indications eg 1s...

Page 4: ...L Y SILENCE FIRE Each function has its own indication LED There are Alarm Active Fault Test Disablement LEDs for most panel inputs outputs Some of these indications are not applicable for certain func...

Page 5: ...tage sounder is on 1S T STAGESNDRFAULT YELLOW Lights when the first stage sounder has a wiring fault 1 S T STAGESNDRTEST YELLOW Lights when the first stage sounder is in test mode 1S T STAGESNDRDISABL...

Page 6: ...tic manual only mode GAS RELEASE COUNTER Used to view or alter Gas Release Counter RELEASE DURATION TIME Used to view or alter Release Duration Time Counter RESET INHIBIT TIME Used to view or alter Re...

Page 7: ...m Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED on 4 If a small fire is found a suitably trained person could tack...

Page 8: ...he second stage cannot be silenced and after a delay period Set by the the installer the extinguishing output will be initiated releasing the extinguishing agent and the second stage sounder will now...

Page 9: ...automatic mode the panel cannot be reset until the reset inhibit timer has finished it s countdown The panel can NOT be reset from a fault condition All faults are non latching so when a fault clears...

Page 10: ...peated Press SELECT button The GENERAL DISABLEMENT LED will light steady and the Crossed Zone 1 Disabled LED will flash 4 quick flashes off The panel is now in SELECT DISABLEMENT MODE The select butto...

Page 11: ...Panel USER MANUAL Approved Document No GLT MAN 132 PAGE 11 Issue 1 2 Author NRPJ Date 06 10 2010 LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQ...

Page 12: ...No GLT MAN 132 PAGE 12 Issue 1 2 Author NRPJ Date 06 10 2010 FALSE ALARMS DATE TIME ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENANCE FINDINGS CATEG...

Page 13: ...el USER MANUAL Approved Document No GLT MAN 132 PAGE 13 Issue 1 2 Author NRPJ Date 06 10 2010 ALL OTHER EVENTS DATE TIME ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIRED DATE CO...

Reviews: