Calibration and Bump Testing
Gas detectors should be functionally tested regularly to ensure their
correct operation. This is referred to as bump testing.
To bump test a Zeta Gas Sense detector, fit the Calibration cap to the stainless
steel filter housing. Then take a test Cylinder with the appropriate gas type &
concentration. Fit the tube from the cylinder to the Calibration cap . Open the
regulator on the cylinder. Check that the reading on the detector rises and reaches
the level indicated on the cylinder (Within the specified tolerance range)
If a detector fails this bump test then it should be zero’s in clean air then
recalibrated using the calibration cap and the gas cylinder.
Test Gas Cylinders
A range of cylinders are available for testing the Gas Sense detectors.
Gas Type
H2S
H2S
H2S
NH3
CO
NO2
O2
Volume Of Test Cylinder
34 Litres
34 Litres
34 Litres
34Litres
34 Litres
34 Litres
34 Litres
Test Gas Concentration
250 ppm
100 ppm
50 ppm
500 ppm
50 ppm
10 ppm
150 ppm
Part Number
31650-3-1
31650-4-1
31650-5-1
31650-7-1
31650-6-1
31650-2-1
31650-1-1
Pressure
500PSI
500PSI
500PSI
500PSI
500PSI
500PSI
500PSI
Other gasses & concentrations are available on request.
15