PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
47
Panel
-
-
RMT/No/Yes (1-032)
Delay
(000–999)
Outputs ON
Outputs OFF
Sounders ON*
Sounders OFF
Relays ON
Relays OFF
PCB Sounder One ON
PCB Sounder One
OFF
PCB Sounder Two ON
PCB Sounder Two
OFF
Alarm + Flash
Alert + Flash
Eme Flash
Flasher
Alarm
Alert
Emergency
Outputs Marked * have the tone selection option
ACTIONS (MODIFY)
For each ACTION (Cause & Effect) previously selected you can:
Change Input Selection, i.e. Point / Zone / Loop / Panel etc.
Change Output Selection, i.e. Point / Zone / Loop / Panel etc.
Erase one or more previous action
Exit to New / Modify
11- DISABLEMENTS
11.1 DISABLEMENT
To aid commissioning and assist routine maintenance checks, various functions of the Quatro fire alarm system can be disabled as
described below.
11.2 ZONE DISABLEMENT
When a zone is disabled, the panel will not respond to any fault or fire signals it receives from DETECTORS from that zone.
This might be used if the system requires routine maintenance, and the user needs the rest of the system to continue running, but
doesn’t want spurious false alarms.
The panel will respond in the usual manner to any events in any non-disabled zones.
Any number of zones can be disabled, but it is good practice to only disable one zone at a time.
A zone can be disabled as follows:
Turn the key switch clockwise to the Controls Enabled Position. The controls Active LED will light.
Press any key followed by the Level 1 password (default 1111).
Select
Zones
then
Disable
. Enter the zone(s) or range of zones to be disabled.
Finally select Accept and then Exit.
When zones have been disabled, the General Disablement LED will be lit and also the zonal disablement LEDs (in one or both of the
columns labelled FAULT DISABLE TEST). The zonal disablement LEDs only apply to zones 1 to 20.
When one or more zones have been disabled, the main screen on the LCD display changes from SYSTEM NORMAL to DISABLED
ZONES, as shown.
In the example, line 2 indicates that a total of 9 zones have been disabled, and
the 5th of these is shown on line 3. Zone 1 (Z001) has the text label FIRST FLOOR.
The zone no. and text label for each disabled zone can be displayed by pressing
18/08/15 09:38
DISABLED ZONES 005/009
Z001 – FIRST FLOOR
[ - ] [ + ]