PRINTER MODULE INSTRUCTION MANUAL 

 

 

TRM RJ45 Port Address Designation 

 

Each RJ45 port on the Smart Connect Multi-loop termination has its own unique port address. This port address is 
important to keep note of as it is displayed on Alarm/Fault messages and is used when configuring or setting up 
cause and effects on the panel (See SCM operation manual GLT-261-7-10). 

 

Securing the modules 

 

The modules are designed to clip together to make them more secure. In addition, the Smart Connect Multiloop 
panel is supplied with Din rail stoppers. These should be fitted before the first module, and after the last module on 
each rail. 

 

Before Powering the Panel On 

 

1.

 

To prevent the risk of a spark, do not connect the batteries. Only connect the batteries after powering on the 

system from its main AC supply. 

2.

 

Check that all external field wiring is clear from any open, shorts and ground faults. 

3.

 

Check that all the modules have been installed properly, with correct connections and placement 

4.

 

Check that all switches and jumper links are at their correct settings. 

5.

 

Check that all interconnection cables are plugged in properly, and that they are secure. 

6.

 

Check that the AC power wiring is correct. 

7.

 

Ensure that the panel chassis has been correctly earth grounded. 

Before powering on from the main AC supply, make sure that the front panel door is closed

 